Alarm Message | Severity | Action Required |
|
|
|
Suction Pressure Sensor Failure | Warning | • Make sure the sensor is connected properly. |
|
| • If the problem persists, replace the sensor or contact APC at a |
|
| number on the back cover of this manual. |
|
|
|
Dischrg Pressure Sensor Failure | Warning | • Make sure the sensor is connected properly. |
|
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Input Contact Fault | Warning | • Make sure the Input Normal state is defined correctly in the |
|
| Configure Unit> Discrete I/O screen. See page 17 for more |
|
| information. |
|
| • Clear the problem that caused the input contact switch to change |
|
| from the normal state. |
|
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Persistent High Discharge | Critical | • Indicates there were three High Discharge Pressure shutdowns in |
Pressure Fault |
| 30 minutes. Alarms must be cleared manually. |
|
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Persistent Low Suction Pressure | Critical | • Indicates there were 3 Low Suction Pressure shutdowns in 30 |
Fault |
| minutes. Alarms must be cleared manually. |
|
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Cannot Start Due to Low | Critical | • The unit cannot start because the suction (low side) refrigerant |
Suction Pressure |
| pressure is too low. |
|
| • For assistance, contact APC at a number on the back cover of this |
|
| manual. |
|
|
|
Superheat too Low | Warning | • For assistance, contact APC at a number on the back cover of this |
|
| manual. |
|
|
|
Rack Inlet | Critical | • Make sure the Rack Inlet setting is correct in the Set Unit |
(Rack Inlet Temperature High |
| Threshlds screen. |
Threshold) |
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Supply Air | Critical | • Make sure the Supply Air setting is correct in the Set Unit |
(Supply Air Temperature High |
| Threshlds screen. |
Threshold) |
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
Return Air | Critical | • Make sure the Return Air setting is correct in the Set Unit |
(Return Air Temperature |
| Threshlds screen. |
HighThreshold) |
| • If the problem persists, contact APC at a number on the back cover |
|
| of this manual. |
|
|
|
InRow RD 10 kW Air Cooled Operation and Maintenance | 31 |