APC ACRD101 Contacts, Cooling Group Configuration, View the state of input and output contacts

Page 25

Contacts

View the state of input and output contacts

Path: Main > Configure Unit > Discrete I/O

Each cooling unit supports a user-defined input contact and a user-defined output contact. Each contact monitors a sensor and responds to changes in the state of the sensor (open or closed).

Input State. Indicates the actual state of the input contact (Open or Closed). A cooling unit is On when the state is normal and in Standby when the state is not normal.

Output State. Indicates the actual state of the output contact (Open or Closed). An alarm will cause the output contact to change from the normal state.

OHE Input State. Indicates the actual state of the input contact (Open or Closed) for the Outdoor Heat Exchanger.

Edit the normal state of input and output contacts

Path: Main > Configure Unit > Discrete I/O > Normal State

Configure the input contacts to cause alarm conditions based onthe user-defined normal state. Output contacts can map internal alarms and events to outside devices.

Input Norm. Set the normal state of the contact (Open or Closed). The cooling unit changes its operating mode to Closed when the actual state differs from the normal state.

Output Norm. Set the normal state of the contact (Open or Closed). If the state of an alarm or event mapped to this contact changes from the normal state, the contact also changes state.

Outpt Src. Define the type of output source (alarm), either Any Alrm or Critical, that causes the output to change from its normal state.

OHE In Norm. Set the normal state of the contact (Open or Closed) for the Outdoor Heat Exchanger.

Cooling Group Configuration

Use the cooling group configuration settings to add cooling units to the group and to define group operation.

Caution: This procedure is to be performed by APC authorized personnel only. The settings in the Configure Group menu are defined by APC authorized personnel when the cooling group is commissioned.

Configure the cooling group

Path: Main > Configure Group

The Configure Group menu contains settings that identify the number of cooling units installed in this cooling group and the physical arrangement of those cooling units.

Num Units. Enter the number of cooling units in this cooling group. Up to 12 cooling units can be joined together to work as a single cooling group.

InRow RD 10 kW Air Cooled Operation and Maintenance

17

Image 25
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Cross-reference symbol used in this manual Symbols used in this manualOverview Safety Initial inspection checklist Inspection ChecklistsEnsure that Electrical inspection checklist Ensure that Mechanical inspection checklistStart-up inspection checklist User interface inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatCalculating R410A charge Charging With RefrigerantInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Compressor Oil Charge Oil charging procedureInRow RD 10 kW Air Cooled Operation and Maintenance Display Interface OperationScrolling status screens Using the Display InterfaceStatus Screen Name Status Information Displayed Main menu screensNavigating the sub-menus Navigating the main menuPassword entry Using the Path statementStart the cooling unit Cooling unit configuration General ConfigurationStop the cooling unit Configure the cooling group Cooling Group ConfigurationContacts View the state of input and output contactsIdentify the cooling unit Configure ModbusSetpoints Control the EnvironmentPID settings Tune the PID loop Loop Behavior PID Tuning CorrectionControl Method Proportional Integral Derivative Run hours Service intervalsThresholds Date and time Password and time-outDisplay units Adjust display settingsConfigure network Network ConfigurationCooling unit status View Status ReadingsAbout the cooling unit Cooling group statusView the event log Event LogClear the event log View active alarms Respond to AlarmsClear active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more TCP/IP configuration methods Quick ConfigurationOverview Bootp & Dhcp configuration APC Device IP Configuration WizardIni file utility NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Remote access to the control console Local access to the control consoleChoose Network from the Control Console menu Control consoleWeb interface Access a Configured Network Management CardTelnet and SSH Modbus Simple Network Management Protocol SnmpRecover From a Lost Password Cleanliness Monthly Preventive MaintenanceEnvironment Electrical MechanicalFunctional tests Semi-Annual Preventive MaintenanceProblem Possible Cause Corrective Action TroubleshootingCorrective Action Problem Possible CausePage Page 990-3212A-001 11/2009 APC Worldwide Customer Support