APC ACRD100, ACRD101 manual Troubleshooting, Problem Possible Cause Corrective Action

Page 52

Troubleshooting

Problem

Possible Cause

Corrective Action

 

 

 

Controls erratic or

• Inlet temperature to cooling

• Reduce the load or add additional cooling equipment.

inoperative

unit is higher than rated

 

 

maximum temperature

 

Fans fail to start

• Power supplies are not

 

operating properly

 

• Failed power supply

 

• Cooling unit shutd own due to

 

an external command

Confirm that the power supplies are seated properly and fully engaged. This is indicated by a green LED.

Confirm that the cooling unit is plugged in and is receiving power.

Replace the power supply if the LED is red.

Temporarily remove the user contact cable, if it is connected.

• Single fan fails to start

• Verify that the fan circuit breaker is ON.

Cooling unit cannot obtain setpoint

• Improper placement of remote

• Verify that the remote temperature sensor is properly located

temperature sensor

in the cold aisle.

• Dirty filter

• Clean the filter.

• Dirty coil

• Clean the coil.

• Application error

• For assistance, contact APC at a number on the back cover of

 

this manual.

 

• Heat load is too far away

• Place the cooling unit closer to the heat load.

Water carryover

• Improper fan speed selected

• RACS and HACS modes only. Select the next highest fan

 

 

speed setting. For example, change the fan speed setting from

 

 

Low to Med/Low.

 

 

 

Temperature control

• Improper placement of remote

• Verify that the remote temperature sensor is properly located

not tight enough

temperature sensor

in the cold aisle.

 

 

 

Water on outside of

• Condensate drain hose is not

• Verify that the condensate drain hose is properly connected to

cooling unit

connected or not properly

the pump and properly routed outside of the cooling unit.

 

routed outside the cooling unit

• Verify that the condensate drain line does not exceed 4.9

 

 

meters (16 feet) lift and 15.4 meters (50.0 feet) horizontal run.

 

• Leak in piping system

• Locate and repair the leak.

 

• Cooling unit not leveled

• Adjust the leveling feet of the cooling unit.

 

properly

 

 

• Damaged piping insulation

• Identify damaged area and repair the insulation.

 

 

 

Display interface not

• Display interface not

• Verify that the display interface cable is connected properly.

operational but

connected properly

 

cooling unit operates

 

 

 

 

 

Incorrect air pressure

• False filter clogs

• Verify that the ends of the clear plastic air tubes are not

 

 

obstructed.

 

 

• Verify that the clear plastic air tubes are connected to the

 

 

controller.

 

 

• Verify that the clear plastic air tubes are not pinched.

Alarms do not show up on monitoring equipment (Customer Output Contact)

External monitoring equipment is not receiving power or is not functioning properly

Confirm that power, if required, is being supplied to the external equipment.

If the cooling unit (+12 V or +24 V) is providing power to the external equipment, verify that the external equipment is <50 mA.

Test the external equipment by bypassing the output contact.

Verify Customer Output Contact settings. See “Contacts” on page 17.

44

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 52
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Cross-reference symbol used in this manual Symbols used in this manualOverview Safety Initial inspection checklist Inspection ChecklistsEnsure that Electrical inspection checklist Mechanical inspection checklist Ensure thatUser interface inspection checklist Start-up inspection checklistFinal inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceUsing the Display Interface Scrolling status screensStatus Screen Name Status Information Displayed Main menu screensNavigating the main menu Navigating the sub-menusPassword entry Using the Path statementStart the cooling unit Cooling unit configuration General ConfigurationStop the cooling unit Cooling Group Configuration Configure the cooling groupContacts View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Tune the PID loop Loop Behavior PID Tuning CorrectionControl Method Proportional Integral Derivative Run hours Service intervalsThresholds Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitView the event log Event LogClear the event log Respond to Alarms View active alarmsClear active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more TCP/IP configuration methods Quick ConfigurationOverview Bootp & Dhcp configuration APC Device IP Configuration WizardIni file utility NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Cleanliness Monthly Preventive MaintenanceEnvironment Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009