Problem | Possible Cause | Corrective Action |
Cooling unit does not • Drive voltage shut down on
command
•Verify that there is a drive voltage entering the input of the cooling unit. You may use the available +12 V or +24 V. You must then also use the ground.
•Verify Customer Input Contact settings. See “Contacts” on page 17.
No communication | • Improper connection | • Confirm that the cooling unit is connected to the BMS port |
with building |
| and not to the Control port. |
management system |
| • Make sure that the wire polarity is correct. |
(BMS) port |
| Using a DC voltmeter, test the signal with no transmissions in |
|
| progress. Pin 2 should be greater than Pin 1 by at least 200 |
|
| mV. Measure the cooling unit with the cable disconnected, |
|
| and then measure it again with the cable connected. If the |
|
| signal is less than 200 mV, the cooling unit may be reverse- |
|
| wired. |
|
| • Make sure that every cooling unit has either two sets of wires |
|
| in its connector or one set of wires and a |
|
| terminating resistor of 100 to 120 ohms). |
Cooling units are not •
each other
•Verify the actual number of cooling units in the group matches the group number setting.
•Verify that the
•Confirm that the
Output air is 17°C (62°F) and fans are running at a very high rate of speed.
•Upper or lower supply air sensor fault
•Either the upper or lower supply air temperature sensor has a fault. Verify that both supply air temperature sensors are installed and working properly.
InRow RD 10 kW Air Cooled Operation and Maintenance | 45 |