APC ACRD100, ACRD101 manual User interface inspection checklist, Start-up inspection checklist

Page 14

User interface inspection checklist

The user interface inspection verifies that the sensors and internal communications links of the cooling unit are installed properly.

Ensure that:

An A-Link bus is connected to each cooling unit in the group and a terminator is plugged into all unused A-Link connectors.

The input contacts and output relays are connected correctly.

The building management system is connected correctly and a terminator is wired into the final unit between Modbus D0 and Modbus D1.

The rack temperature sensors are installed correctly.

The network port is connected correctly and an IP address has been assigned to the equipment.

Start-up inspection checklist

The start-up inspection ensures that the cooling unit is operating properly after the initial start-up. This inspection verifies that all modes of operation are working correctly and that the cooling unit is ready for normal operation.

While the cooling unit is operating, ensure that the:

Cooling unit is free from malfunctions, unusual vibrations, or other irregularities in each mode of operation.

Cool cycles engage.

Air filters are clean and free of debris. Replace air filters with APC part number 875-2013.

Clogged filter alarm is operating properly:

Cover 1/3 of the filter area and monitor alarm performance.

Compressor suction and discharge pressures are recorded.

Sight glass moisture sensor is green.

Final inspection checklist

The final inspection verifies that the system is clean and the start-up form has been sent to APC.

Ensure that:

System is clean and free from debris.

Packaging materials are disposed of properly.

Start-up form was completed and sent to APC.

6

InRow RD 10 kW Air Cooled Operation and Maintenance

Image 14
Contents Operation and Maintenance 동봉된 CD 안에 한국어 매뉴얼이 있습니다 American Power Conversion Legal Disclaimer Page Contents Cooling Group Configuration Network Management Card Page Overview Symbols used in this manualCross-reference symbol used in this manual Safety Ensure that Inspection ChecklistsInitial inspection checklist Electrical inspection checklist Mechanical inspection checklist Ensure thatFinal inspection checklist User interface inspection checklistStart-up inspection checklist While the cooling unit is operating, ensure thatCharging With Refrigerant Calculating R410A chargeInRow RD 10 kW Air Cooled Operation and Maintenance Charging the equipment Oil charging procedure Compressor Oil ChargeInRow RD 10 kW Air Cooled Operation and Maintenance Operation Display InterfaceStatus Screen Name Status Information Displayed Using the Display InterfaceScrolling status screens Main menu screensNavigating the main menu Navigating the sub-menusStart the cooling unit Using the Path statementPassword entry Stop the cooling unit General ConfigurationCooling unit configuration Contacts Cooling Group ConfigurationConfigure the cooling group View the state of input and output contactsConfigure Modbus Identify the cooling unitControl the Environment SetpointsPID settings Control Method Proportional Integral Derivative Loop Behavior PID Tuning CorrectionTune the PID loop Thresholds Service intervalsRun hours Password and time-out Date and timeAdjust display settings Display unitsNetwork Configuration Configure networkView Status Readings Cooling unit statusCooling group status About the cooling unitClear the event log Event LogView the event log Clear active alarms Respond to AlarmsView active alarms Alarm messages and suggested actionsThreshlds screen Configure Unit Discrete I/O screen. See page 17 for more Overview Quick ConfigurationTCP/IP configuration methods Ini file utility APC Device IP Configuration WizardBootp & Dhcp configuration NetworkTCP/IPBoot ModeDHCP onlyAdvancedDHCP Cookie Is Local access to the control console Remote access to the control consoleControl console Choose Network from the Control Console menuAccess a Configured Network Management Card Web interfaceTelnet and SSH Simple Network Management Protocol Snmp ModbusRecover From a Lost Password Environment Monthly Preventive MaintenanceCleanliness Mechanical ElectricalSemi-Annual Preventive Maintenance Functional testsTroubleshooting Problem Possible Cause Corrective ActionProblem Possible Cause Corrective ActionPage Page APC Worldwide Customer Support 990-3212A-001 11/2009