Empire Comfort Systems DVP48FP7, DVP48FP3 Venting Fireplace TOP, Below Grade Installation

Page 15

VENTING FIREPLACE - TOP (continued)

Below Grade Installation

When it is not possible to meet the required vent terminal clearances of 12" (305mm) above grade level, a snorkel kit is recommended. It allows installation depth down to 7" (178mm) below grade level. The 7" (178mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.

Ensure the sidewall venting clearances are observed. If venting system is installed below ground, we recommend a window well with adequate and proper drainage to be installed around the termination area.

TYPICAL BASEMENT INSTALLATION

Figure 20

Examples of possible venting systems using one (1) 90° elbow. Eight (8) feet is listed as minimum vertical vent run with 20 feet of maximum horizontal vent run. Vertical dimensions are based on centerline to centerline of pipe. Horizontal dimensions are based on centerline of pipe to end of termination.

Firestop at

Ceiling Level

Figure 21

Examples of possible venting systems using two (2) 90° elbows. V is listed as minimum vertical dimensions and H1 + H2 is listed as total of maximum horizontal dimensions. The maximum vertical and horizontal distances for two (2) 90° elbows as shown in Figure 22 is 20 feet.

Attention: Refer to Figure 19 for additional venting requirements.

Firestop at

Ceiling Level

Figure 22

17375-6-0705

Page 15

Image 15
Contents Installation Instructions Table of Contents Important Safety Information LP-GAS Warning Odor Safety Information for Users of LP GASIntroduction Fireplace Dimensions SpecificationsClearances Figure Mantel Chart FigureClearances Locating FireplaceInstalling a New Main Gas Cock GAS SupplyChecking Manifold Pressures Rear Vent Conversion Vent SystemsConverting flue take-off to rear venting Installation Framing and FinishingVent Pipe Clearance Flush Mount Mantel Installation Figure Framing FigureFinishing Figures 12 VERTICAL, 90 Elbow with Horizontal Termination Flush Wall Installation Combustible Surround Installation Vent Runs Figures 14, 15, 16, 17Model VERTICAL, 90 Elbow toExample a Venting Graph Dimensions in FeetVenting Fireplace TOP To Use the Vent Graph FigureVenting Fireplace TOP Below Grade InstallationFireplace Hard Elbow Dimensions Series DVP42FP Examples TOP Vent RUN Theunit Caps Venting Fireplace RearExamples Rear Vent RUN Vertical Sidewall Installations Termination ClearancesInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureInstalling Support Brackets Figure Installing Firestops Figures 38, 39, 40Framing and Finishing See Horizontal Termination Page 24 and Vertical Termination Horizontal TerminationDVVK-5F Flex Vent Instructions Determining Minimum Vent Height Above the Roof General MaintenanceInstalling the Vent System in a Chase Vertical TerminationVertical Termination Reassembly and Resealing Vent Pipe SystemLOG Placement 3 LOG SET Pilot Flame Figure Operating InstructionsMillivolt System Initial LightingTRW Standing Pilot Wiring Diagram Standing Pilot Lighting Instructions For Your Safety Read Before LightingGlass soots Standing Pilot TroubleshootingFrequent pilot outage problem Pilot and main burner extinguish while in operationElectrical Connection Figure Intermittent Pilot Operating InstructionsWhat to do if YOU Smell GAS For Your Safety Read Before LightingTrial for Ignition S8600H Intermittent Ignition Module SpecificationsCheckout OperationMain Burner Operation Safety LockoutARC Length Action Ignition System Checks Check ignition cable. Make sureIntermittent Pilot Troubleshooting Thermopiles Transmitter SignalFunctions Receiver Shutdown of BurnerRF Transmitter Functions Wiring Diagram with Blower RF Standing Pilot Lighting Instructions Please Note Maintenance and ServiceParts View Parts List Blower Wheels Blower MotorVolt AC Optional Brick Liner Installation Instructions Junction BOX Wiring Installation InstructionsFBB4 AccessoriesService Notes HOW to Order Repair Parts Service Notes