Burnham MMII manual Horizontal Vent Pipe Wall Penetration, Vertical Through Roof Vent Installation

Page 16

d.Minimum 4 feet (6 feet in Canada) horizontally from electric meters, gas meters, regulators, and relief equipment.

e.Minimum 12 inches from overhang or corner.

3.Use double wall thimble when passing through combustible outside wall (thimble use optional for noncombustible wall). Insert thimble through wall from outside. Secure outside flange to wall with nails or screws, and seal OD, ID and vent holes with sealant material. Install inside flange to inside wall, secure with nails or screws, and seal with sealant material.

4.For noncombustible wall when thimble is not used, size opening such that female (bell) end with locking band attached cannot pass through.

5.Join vent terminal to vent pipe. Locate vent terminal between 3" and 6" from wall when joined to inside vent piping. See Figure 13.

Figure 13: Horizontal Vent Pipe Wall Penetration

Figure 14: Horizontal Air Intake Pipe Wall

Penetration

6.Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.

Figure 15: Vent/Air Intake Terminal Relationship

Horizontal (thru wall) or Vertical (thru roof)

I.Vertical (Through Roof) Vent Installation

1.Install vertical vent drain tee (see Table 7 for part number). See Figure 16. Attach tee directly to elbow or horizontal pipe from elbow.

2.Install condensate drain line. Use 3/8 inch i.d. high temperature flexible tubing such as silicone rubber or EPDM. See Figure below.

a.Form condensate trap with 6 inch diameter loop. Secure loop with plastic cable tie. Fill with water.

16

Image 16
Contents Minuteman 81404025R13-1/07 Price $3.00Table of Contents Dimensional Drawing Pre-Installation Minimum Clearances to Combustible SurfacesIII. Water Piping and Trim II. Unpack BoilerDo not drop boiler. Do not bump boiler jacket against floor Page Internal Water Piping System Diagram IV. Domestic Hot Water Performance and Piping Domestic Hot Water RatingsGas Piping Rated InputFitting Equivalent Lengths Specific Gravity Correction FactorsVI. Venting / Air Intake Piping ComponentGeneral Guidelines Vent/Air Intake LengthInstall Vent Connector Burnham Vent System ComponentsInstall Vent Pipe, Burnham Gasket-Less Vent System Install Vent Pipe, GeneralInstall Vent Pipe, Burnham Gasketed Vent System Horizontal Through Wall Vent Installation Burnham Gasketed Vent Joint DetailRecommended Horizontal Vent Installation Vertical Through Roof Vent Installation Horizontal Vent Pipe Wall PenetrationVertical Vent Installation Install Air Intake PipeWiring Diagram VII. ElectricalVIII. System Start-up Do not install an automatic fill valve with this boilerPrepare to check operation Operating Instructions Adjust gas input rate to boiler Check Boiler High LimitGas Flow Rate in Cubic Feet per Hour IX. Service Main Burners and Combustion Chamber LubricationBurner and Flueway Cleaning Differential Pressure Switch Settings Pilot Burner LocationAvoid Breathing Fiber Particulates and Dust Page Page Repair Parts Heat Exchanger AssemblyCanopy/Blower Assembly Cerafelt Gasketing not depictedPage Page Base Assembly Page Page Jacket Assembly Domestic Water Tank Assembly Miscellaneous Trim and Controls Vent Accessory Carton Air Intake TerminalLimited Warranty