Burnham MMII manual Vertical Vent Installation, Install Air Intake Pipe

Page 17

Figure 16: Vertical Vent Installation

b.Secure to vertical vent tee with hose clamp or plastic cable tie.

c.Run condensate drain line to floor drain or condensate pump. Condensate disposal must be acceptable to authority having jurisdiction.

3.Slope horizontal runs minimum ¼ inch per foot. Slope toward vertical vent drain tee. Position weld seams in vent pipes in all horizontal runs at the top to avoid condensate from lying on the seams.

4.Install firestops at floor and ceiling where vent passes through floor, ceiling, or framed wall. The firestop must close the floor or ceiling opening between vent pipe and structure. Firestop manufacturers are Air-Jet, American Metal Products, Metal-Fab, and Simpson Dura-Vent.

5.Enclose vent passing through unoccupied or occupied spaces above the appliance with materials having a fire resistance rating at least equal to the rating of adjoining floor or ceiling. Maintain 5 inch minimum clearance to combustible materials. Note: For one-or two-family dwellings fire resistance rating requirement may not need to be met, but is recommended.

6.Whenever possible install vent straight through roof. Refer to Figure 17 if offset is necessary. Maintain 5 inch minimum clearance to combustible materials.

7.Install Vent Terminal. See Figure 18.

a.Locate roof opening to allow vertical vent penetration. Size opening to maintain 5 inch minimum clearance from combustible materials.

b.Vertical venting requires use of roof flashing (available from Burnham - P/N 8116250) and storm collar (available from Burnham - P/N 8116251) to prevent moisture from entering the structure.

c.Extend vent pipe to maintain minimum vertical and horizontal distance of 12 inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figure 18.

d.Install storm collar on vent pipe immediately above roof flashing. Apply Dow Corning Silastic 732 RTV Sealant between vent pipe and storm collar to provide weathertight seal..

e.Attach Vent Terminal.

J. Install Air Intake Pipe.

1.Locate air intake termination on the same wall or roof location as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler

Figure 17: Attic Offset

Figure 18: Vertical Vent Termination

Figure 19: Vertical Air Intake Termination

Extend Vent/Air Intake Piping to maintain minimum vertical ("X") and minimum horizontal ("Y") distance

of twelve (12) inches from roof surface. Allow additional vertical ("X") distance for expected snow

17

Image 17
Contents 81404025R13-1/07 Price $3.00 MinutemanTable of Contents Dimensional Drawing Minimum Clearances to Combustible Surfaces Pre-InstallationDo not drop boiler. Do not bump boiler jacket against floor II. Unpack BoilerIII. Water Piping and Trim Page Internal Water Piping System Diagram Domestic Hot Water Ratings IV. Domestic Hot Water Performance and PipingRated Input Gas PipingSpecific Gravity Correction Factors Fitting Equivalent LengthsComponent VI. Venting / Air Intake PipingGeneral Guidelines Vent/Air Intake LengthBurnham Vent System Components Install Vent ConnectorInstall Vent Pipe, Burnham Gasketed Vent System Install Vent Pipe, GeneralInstall Vent Pipe, Burnham Gasket-Less Vent System Burnham Gasketed Vent Joint Detail Horizontal Through Wall Vent InstallationRecommended Horizontal Vent Installation Horizontal Vent Pipe Wall Penetration Vertical Through Roof Vent InstallationInstall Air Intake Pipe Vertical Vent InstallationVII. Electrical Wiring DiagramPrepare to check operation Do not install an automatic fill valve with this boilerVIII. System Start-up Operating Instructions Check Boiler High Limit Adjust gas input rate to boilerGas Flow Rate in Cubic Feet per Hour IX. Service Lubrication Main Burners and Combustion ChamberBurner and Flueway Cleaning Pilot Burner Location Differential Pressure Switch SettingsAvoid Breathing Fiber Particulates and Dust Page Page Heat Exchanger Assembly Repair PartsCanopy/Blower Assembly Cerafelt Gasketing not depictedPage Page Base Assembly Page Page Jacket Assembly Domestic Water Tank Assembly Miscellaneous Trim and Controls Air Intake Terminal Vent Accessory CartonLimited Warranty