Burnham MMII manual Gas Flow Rate in Cubic Feet per Hour

Page 22

4.Determine Input Rate. Multiply gas flow rate by gas heating value.

5.Compare measured input rate to input rate stated on rating plate.

a.Boiler must not be overfired. Reduce input rate by decreasing manifold pressure. Do not reduce more than 0.2 inch w.c. If boiler is still overfired, contact your Burnham distributor or Regional Office for replacement Gas Orifices.

b.Increase input rate if less than 98% of rating plate input. Increase manifold gas pressure no more than 0.2 inch w.c. If measured input rate is still less than 98% of rated input:

i.Remove Main Burners per procedure in Section IX: Service.

ii.Remove gas orifices. Drill one (1) drill size larger (drill size is stamped on orifice, or see Key No. 4C in Section X: Repair Parts).

iii.Reinstall gas orifices and main burners. Measure input rate.

6.Recheck Main Burner Flame.

7.Return other gas fired appliances to previous conditions of use.

N. Review User's Information Manual and system operation with owner or operator.

Table 9: Gas Flow Rate in Cubic Feet per Hour

Seconds

Size of Gas Meter Dial

 

 

 

for One

One-Half

One

Two

Revolution

Cu. Ft.

Cu. Ft.

Cu. Ft.

 

 

 

 

 

30

60

120

240

 

 

 

 

32

56

113

225

 

 

 

 

34

53

106

212

 

 

 

 

36

50

100

200

 

 

 

 

38

47

95

189

 

 

 

 

40

45

90

180

 

 

 

 

42

43

86

172

 

 

 

 

44

41

82

164

 

 

 

 

46

39

78

157

 

 

 

 

48

37

75

150

 

 

 

 

50

36

72

144

 

 

 

 

52

35

69

138

 

 

 

 

54

33

67

133

 

 

 

 

56

32

64

129

 

 

 

 

58

31

62

124

 

 

 

 

60

30

60

120

 

 

 

 

22

Image 22
Contents Minuteman 81404025R13-1/07 Price $3.00Table of Contents Dimensional Drawing Pre-Installation Minimum Clearances to Combustible SurfacesIII. Water Piping and Trim II. Unpack BoilerDo not drop boiler. Do not bump boiler jacket against floor Page Internal Water Piping System Diagram IV. Domestic Hot Water Performance and Piping Domestic Hot Water RatingsGas Piping Rated InputFitting Equivalent Lengths Specific Gravity Correction FactorsGeneral Guidelines VI. Venting / Air Intake PipingComponent Vent/Air Intake LengthInstall Vent Connector Burnham Vent System ComponentsInstall Vent Pipe, Burnham Gasket-Less Vent System Install Vent Pipe, GeneralInstall Vent Pipe, Burnham Gasketed Vent System Horizontal Through Wall Vent Installation Burnham Gasketed Vent Joint DetailRecommended Horizontal Vent Installation Vertical Through Roof Vent Installation Horizontal Vent Pipe Wall PenetrationVertical Vent Installation Install Air Intake PipeWiring Diagram VII. ElectricalVIII. System Start-up Do not install an automatic fill valve with this boilerPrepare to check operation Operating Instructions Adjust gas input rate to boiler Check Boiler High LimitGas Flow Rate in Cubic Feet per Hour IX. Service Main Burners and Combustion Chamber LubricationBurner and Flueway Cleaning Differential Pressure Switch Settings Pilot Burner LocationAvoid Breathing Fiber Particulates and Dust Page Page Canopy/Blower Assembly Repair PartsHeat Exchanger Assembly Cerafelt Gasketing not depictedPage Page Base Assembly Page Page Jacket Assembly Domestic Water Tank Assembly Miscellaneous Trim and Controls Vent Accessory Carton Air Intake TerminalLimited Warranty