Omega RD100B manual Cu10, Cu25 RTD Input /N1, Legs Isolated RTD /N2, Expansion Inputs /N3

Models: RD100B

1 234
Download 234 pages 60.28 Kb
Page 217
Image 217

 

 

12.5 Specifications of Optional Functions

 

 

 

 

Alarms

 

 

Number of alarms

Up to four alarms (level) for each measurement channels.

 

Alarm types

High limit (H), low limit (L), delay high limit (T), delay low limit (t). The alarm symbol is shown in parentheses.

 

 

Alarm delay time of delay high and low limit alarms (can be set for each channel, common within a

 

 

channel) See section 12.2

 

Hysteresis

Applied to high limit alarm and low limit alarm.

 

 

Hysteresis range: Approx. 0.0% to 1.0% of the recording span (0.1% steps)

 

Miscellaneous

See section 12.2.

 

 

 

 

Display

See section 12.4.

 

 

 

Cu10, Cu25 RTD Input (/N1)

 

 

 

 

Item

Specifications

 

 

 

 

Cu10, Cu25 RTD

This option allows Cu10 and Cu25 inputs to be added to the standard input types.

Input type and measurable range

 

 

Input Type

 

Measurable Range

 

 

 

Cu10 (GE)

 

 

 

 

 

Cu10 (L&N)

 

 

 

 

RTD

Cu10 (WEED)

 

–200 to 300°C

 

 

(Measurement

Cu10 (BAILEY)

 

 

 

 

–328.0 to 572.0°F

 

 

current i: 2 mA)

Cu10: α = 0.00392 at 20°C

 

 

 

 

 

 

 

 

Cu10: α = 0.00393 at 20°C

 

 

 

 

 

Cu25*: α = 0.00425 at 0°C

 

 

 

 

 

 

 

 

 

 

 

* Measurement current i = 1 mA

 

 

 

 

Measurement and recording accuracy

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Type

 

Measurement Accuracy

 

Recording Accuracy

 

 

Cu10 (GE)

 

 

 

 

 

 

Cu10 (L&N)

 

 

 

 

 

 

Cu10 (WEED)

 

±(0.4% of rdg + 1.0°C)

 

Measurement accuracy

 

 

Cu10 (BAILEY)

 

 

± (0.3% of recording span)

 

 

 

 

 

 

 

Cu10: α = 0.00392 at 20°C

 

 

 

 

 

Cu10: α = 0.00393 at 20°C

 

 

 

 

 

Cu25: α = 0.00425 at 0°C

±(0.3% of rdg + 0.8°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 Legs Isolated RTD (/N2)

Item

Specifications

Input terminal isolation

Applies to the dot model.

 

The RTD input terminals are isolated between channels (on the standard dot model, input terminal b

 

are common to all channels)

 

 

Expansion Inputs (/N3)

 

Item

Specifications

 

 

 

 

 

Input type

Adds the input types shown in the table below.

 

 

 

 

 

 

 

 

 

Input Type

Measurement Range

 

 

 

 

 

 

 

 

 

 

 

PR40-20

0.0 to 1900.0°C

32 to 3452°F

 

 

 

 

 

 

 

 

 

 

 

PLATINEL

0.0 to 1400.0°C

32 to 2552°F

 

 

 

Thermocouple

 

 

 

 

 

 

NiNiMo

0.0 to 1310.0°C

32 to 2390°F

 

 

 

 

 

 

 

 

 

 

 

W/WRe26

0.0 to 2400.0°C

32 to 4352°F

 

 

 

 

Type N (AWG14)

0.0 to 1300.0°C

32 to 2372°F

 

 

 

 

Kp vs Au7Fe

0.0 to 300.0 K

 

 

 

 

 

 

 

 

 

 

 

 

Pt25

–200.0 to 550.0°C

–328.0 to 1022.0°F

 

 

 

 

 

 

 

 

 

 

 

Pt50

–200.0 to 600.0°C

–328.0 to 1112.0°F

 

 

 

 

 

 

 

 

 

 

 

Ni100 (SAMA)

–200.0 to 250.0°C

–328.0 to 482.0°F

 

 

 

RTD

 

 

 

 

 

 

Ni100 (DIN)

–60.0 to 180.0°C

–76.0 to 356.0°F

 

 

 

(Measuring current

 

 

 

 

 

 

Ni120

–70.0 to 200.0°C

–94.0 to 392.0°F

 

 

 

 

 

 

 

 

 

i = 1 mA)

J263*B

0.0 to 300.0 K

 

 

 

 

 

 

 

 

 

 

 

 

Cu53

–50.0 to 150.0°C

–58.0 to 302.0°F

 

 

 

Cu100: α = 0.00425 at 0°C

–50.0 to 150.0°C

–58.0 to 302.0°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Specifications

12-15

Page 217
Image 217
Omega RD100B manual Cu10, Cu25 RTD Input /N1, Legs Isolated RTD /N2, Expansion Inputs /N3, Specifications 12-15