Omega RD100B manual 5V Input, Scale Left and Scale Right, Low-cut, Select the right scale value

Models: RD100B

1 234
Download 234 pages 60.28 Kb
Page 100
Image 100

5.1 Setting the Input range

1-5V Input

Set=Range

CH=01-01

First channel Last channel

Mode=1-5V

Span_L= 1,000

Set the channel range.

Select 1-5V.

Set the left span value.

Span_R= 5,000

Scale_L= 0.00

Scale_R=200.00

(Select the right scale value.)

Low-cut=Off

01-01 Channel ESC/? Setting complete

Description

• Span Left and Span Right

Set the right span value.

Set the left scale value.

Set the right scale value.

Turn On or Off the low-cut function.

The new setting takes effect.

Selectable span left range: 0.8 to 1.2 V

Selectable span right range: 4.8 to 5.2 V

Scale Left and Scale Right

Selectable range (mantissa): –20000 to 30000

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX The decimal position is the position specified by scale left. Make sure that scale left is less than scale right.

Low-cut

On: Cuts values below 0% of the recording span (set to 0% (scale left value)).

Off: Does not apply the low-cut function.

Note

The displayable/printable range of scale values is –19999 to 30000 excluding the decimal.

If the leftmost value of the scale is set to –20000 (excluding the decimal), the value when the low-cut function is applied is displayed as “–Over.”