1.8 Remote Control Function (/R1 Option)

Specified operations can be carried out by applying remote signals (contact or open collector signals) to the remote control input terminals.

There are five remote control input terminals. An action can be assigned to each terminal.

R10000 Recorder

Contact

Open collector

Assignable Functions

Recording start/stop

Remote input signal: Rising edge signifies start; falling edge signifies stop

Starts/stops recording.

Applying a rising edge signal when recording is already in progress produces no effect. Applying a falling edge signal when recording is stopped produces no effect.

Chart Speed Switch

Remote input signal: Level

The chart paper is fed at the secondary chart speed while a level signal is applied to the terminal. The secondary chart speed is set in advance.

Message 1 Printout to Message 5 Printout

Remote input signal: Trigger

Prints message 1 to 5 on the chart paper.

Manual Printout

Remote input signal: Trigger

Executes a manual printout.

Alarm ACK

Remote input signal: Trigger

Alarm ACK is executed on all alarms that are occurring. This is valid only when the alarm indication or output relay operation is set to hold.

Internal Clock Adjustment

Remote input signal: Trigger

The internal clock of the recorder is adjusted to the nearest hour depending on the time when the remote signal is applied.

Time When Signal Is Input

Adjustment

00 min 00 s to 01 min 59 s Truncates the minutes and seconds.

Example: 10 hours 01 min 50 s becomes 10 hours 00 min 00 s.

02 min 00 s to 57 min 59 s

The time is not changed.

58 min 00 s to 59 min 59 s Rounds up the minutes and seconds.

Example: 10 hours 59 min 50 s becomes 11 hours 00 min 00 s.

1-28

Page 42
Image 42
Omega RD100B manual Remote Control Function /R1 Option