6.3 Setting the Moving Average (Dot Model)

This section explains the details of setting the moving average function on measurement channels on the dot model.

Procedure

1.Hold down the MENU key for 3 seconds to enter Setting mode.

2.Press the key or SHIFT + key to select Aux and then press the key.

3.Press the key or SHIFT + key to select Moving_AVE and then press the key.

4.Set each item and press the key.

Use the key or SHIFT + key to select values.

For the procedure on how to enter values or characters, see section 4.2.

If you press the ESC key in the middle of the operation, the settings entered up to then are cancelled, and the display returns to a higher level menu.

5.When the Setting complete screen appears, do either of the following: Press the key to set other channels.

If you are done, press the ESC key.

6.Hold down the MENU key for 3 seconds to return to Operation mode.

Set=Aux

Aux=Moving_AVE

CH=

01

-01

Set the channel range.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

First channel Last channel

No.of samples=Off Set the number of samples of the moving average. Moving average is not performed when Off is selected.

ESC/?

01-01 Channel

The new setting takes effect.

Setting complete

 

Explanation

The Number of Samples of Moving Average

The number of samples can be set to a integer between 2 and 16. Select Off when not using the moving average function.

<Related Topics>

Enabling the moving average function: Section 7.11

6

Setup Operations

for Convenient Functions (Setting Mode)

6-3

Page 111
Image 111
Omega RD100B manual Setting the Moving Average Dot Model, Number of Samples of Moving Average, New setting takes effect