7.15Enabling the Bias Function, Low-Cut Function, and Alarm Delay Function

This section explains the details of enabling/disabling the bias function, low-cut function, and the alarm delay function.

Basic Setting mode cannot be entered when recording is in progress or when computation is in progress on models with the computation function (/M1 option).

Procedure

Changing the Settings

1.Hold down the MENU key for 3 seconds to enter Setting mode.

2.Hold down the and keys simultaneously for 3 seconds to enter Basic Setting mode.

3.Press the key or SHIFT + key to select Personalize and then press the key.

4.Press the key with Add function shown on the screen.

5.Set each item and press the key.

Use the key or SHIFT + key to select values.

For the procedure on how to enter values or characters, see section 4.2.

If you press the ESC key in the middle of the operation, the settings entered up to then are cancelled, and the display returns to a higher level menu.

6.When the Setting complete screen appears, do either of the following:

To correct the setting, press the key. If you are done, press the ESC key.

7

Basic=Personalize

Mode=Add function

Bias=Not

SQRT low-cut=Use

1-5V low-cut=Not

Alarm delay=Not

Personalize

ESC/? Setting complete

Enable/Disable the bias function.

Enable/Disable the low-cut function on channels set to square root computation.

Enable/Disable the low-cut function on channels set to 1-5V.

Enable/Disable the alarm delay function.

The new setting takes effect.

Setup Operations

for Changing/Adding Functions (Basic Setting Mode)

Applying the Changes and Returning to Operation Mode

Press the key or SHIFT + key to select End and then press the key. Press

the key to select Store and then press the key. The changes are applied, and the screen returns to Operation mode. If you select Abort and press the key, the changes are discarded, and the screen returns to Operation mode. Press the ESC key to return to the Basic= screen.

7-23

Page 146