6.10 Setting the Alarm Delay Duration

This section explains the details of setting the duration of the delay alarm.

Procedure

1.Hold down the MENU key for 3 seconds to enter Setting mode.

2.Press the key or SHIFT + key to select Aux and then press the key.

3.Press the key or SHIFT + key to select Alarm delay and then press the key.

4.Set each item and press the key.

Use the key or SHIFT + key to select values.

For the procedure on how to enter values or characters, see section 4.2.

If you press the ESC key in the middle of the operation, the settings entered up to then are cancelled, and the display returns to a higher level menu.

5.When the Setting complete screen appears, do either of the following:

Press the key to set other channels. If you are done, press the ESC key.

6.Hold down the MENU key for 3 seconds to return to Operation mode.

Set=Aux

Aux=Alm delay T

CH=01-01

First channel Last channel

Duration= 10

Set the channel range.

Set the alarm delay time.

ESC/?

01-01 Channel

Setting complete

Explanation

Duration

The new setting takes effect.

The duration can be set to a value in the range of 1 to 3600 s.

However, if the scan interval on the dot model is 2.5 s, the actual duration is an integer multiple of 2.5 s. If the set value is not equal to an integer multiple of 2.5 s, the duration is the smallest integer multiple of 2.5 s greater than the set value.

Example: The actual duration for 1 s and 2 s is 2.5 s.

<Related Topics>

Enabling the alarm delay function: Section 7.15

6-10

Page 118
Image 118
Omega RD100B manual Setting the Alarm Delay Duration, Duration New setting takes effect