Chapter 5 Frequently Used Setup Operations (Setting Mode)

5.1 Setting the Input Range

Input range is set for each measurement channel. Set unused channels to Skip.

The input range cannot be changed on models with the computation function (/M1 option) when computation is in progress.

If you change the input range, set the bias, alarm, and partial expanded recording again.

Procedure

TC, RTD, and DC Voltage

1.Hold down the MENU key for 3 seconds to enter Setting mode.

2.Press the key with Range shown on the screen.

3.Set each item and press the key.

Use the key or SHIFT + key to select values.

For the procedure on how to enter values or characters, see section 4.2.

If you press the ESC key in the middle of the operation, the settings entered up to then are cancelled, and the display returns to a higher level menu.

4.When the Setting complete screen appears, do either of the following: Press the key to set other channels.

If you are done, press the ESC key.

5.Hold down the MENU key for 3 seconds to return to Operation mode.

Set=Range

5

Frequently Used Setup Operations

CH=01-01

First channel Last channel

Mode=TC

Range=R

Span_L= 0.0

Span_R=1760.0

01-01 Channel ESC/? Setting complete

Set the channel range.

Select TC, RTD, or Volt.

Select the range type.

Select the left span value.

Select the right span value.

The new setting takes effect.

(Setting Mode)

5-1