Burnham MMII manual Check Boiler High Limit, Adjust gas input rate to boiler

Page 21

Figure 23: Main Burner Flame

Figure 24: Pilot Burner Flame

20°F below boiler high limit setting to allow tank water to reach desired temperature before boiler water reaches the high limit setting.

J. Ignition system safety device test. Disconnect ignitor/ sensor cable from Terminal 9 (SPARK). Gas valve should close and pilot and main burners should extinguish.

K.Check water pressure switch.

1.Adjust thermostat to highest setting.

2.Connect hose to drain valve and run to bucket or floor drain. With boiler operating, partially open drain valve and slowly drain boiler.

3.Main burners and pilot burner will extinguish and blower stop when water pressure drops below 10 psi. Verify limit, thermostat or other controls have not shut off boiler.

4.Close drain valve.

5.Adjust thermostat to lowest setting. Refill boiler.

L.Check Boiler High Limit.

1.Adjust thermostat to highest setting.

2.Observe temperature gauge. When temperature is indicated, adjust limit to setting below observed temperature. Main burners and pilot burner should extinguish, and blower stop.

3.Adjust limit to setting above observed temperature. Ignition sequence should begin.

4.Adjust thermostat to lowest setting. Adjust limit to desired setting, at least 20°F above the tank aquastat setting.

M.Adjust gas input rate to boiler.

1.Adjust thermostat to highest setting.

2.Check manifold gas pressure. Pressure should be stamped on the rating label located in the boiler's vestibule compartment. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure cannot be attained, check gas valve inlet pressure. If less than minimum indicated on the boiler's rating label, contact gas supplier for assistance.

3.Clock gas meter for at least 30 seconds. Use Table 9 to determine gas flow rate in Cubic Feet per Hour.

21

Image 21
Contents 81404025R13-1/07 Price $3.00 MinutemanTable of Contents Dimensional Drawing Minimum Clearances to Combustible Surfaces Pre-InstallationII. Unpack Boiler III. Water Piping and TrimDo not drop boiler. Do not bump boiler jacket against floor Page Internal Water Piping System Diagram Domestic Hot Water Ratings IV. Domestic Hot Water Performance and PipingRated Input Gas PipingSpecific Gravity Correction Factors Fitting Equivalent LengthsComponent VI. Venting / Air Intake PipingGeneral Guidelines Vent/Air Intake LengthBurnham Vent System Components Install Vent ConnectorInstall Vent Pipe, General Install Vent Pipe, Burnham Gasket-Less Vent SystemInstall Vent Pipe, Burnham Gasketed Vent System Burnham Gasketed Vent Joint Detail Horizontal Through Wall Vent InstallationRecommended Horizontal Vent Installation Horizontal Vent Pipe Wall Penetration Vertical Through Roof Vent InstallationInstall Air Intake Pipe Vertical Vent InstallationVII. Electrical Wiring DiagramDo not install an automatic fill valve with this boiler VIII. System Start-upPrepare to check operation Operating Instructions Check Boiler High Limit Adjust gas input rate to boilerGas Flow Rate in Cubic Feet per Hour IX. Service Lubrication Main Burners and Combustion ChamberBurner and Flueway Cleaning Pilot Burner Location Differential Pressure Switch SettingsAvoid Breathing Fiber Particulates and Dust Page Page Heat Exchanger Assembly Repair PartsCanopy/Blower Assembly Cerafelt Gasketing not depictedPage Page Base Assembly Page Page Jacket Assembly Domestic Water Tank Assembly Miscellaneous Trim and Controls Air Intake Terminal Vent Accessory CartonLimited Warranty