TTW1 Universal Service

Replacement Blower

M1TW Series

Step 12. Find the rubber vent adapter kit, P/N

239-46263-00, provided with the blower

kit. Install the 2” vent adapter on the exhaust side of the universal blower.

Discard the vent terminal included with

the vent adapter kit.

Be sure that vent pipe is properly

seated in the top side of vent adapter.

Note: In order to prevent condensate from draining

 

Rubber vent adapter

back into the blower (vertical or horizontal runs),

 

an optional condensate kit is available as a

 

 

service part (Condensate kit, P/N 239-45875-00).

 

Adequately tighten both

 

 

 

Step 13.

If the new adapter is used, remove the old

clamps on the vent adapter.

 

vent adapter from the existing vent pipe.

 

Step 14. Be sure that both clamps on the vent adapter are firmly tightened, securing the blower, vent adapter, and vent pipe together.

 

 

Plug power cord

Step 15.

Double-check all vent connections.

back into outlet.

Step 16.

Restore electrical power to the water

 

 

heater.

 

Turn switch on gas

valve to “On” position.

Step 17. On the water heater's gas control, turn the

power switch to the “On” position.

Warning:

Check all safety devices to make sure they

 

are working properly. Improper water heater

 

operation could occur if these devices are not

 

functioning properly.

Page 26

Image 26
Contents Instructions for Model Numbers Reference Kit Components Tools Required Bradford White TTW1 Universal Service Replacement Blower Step Remove the screws, qty , that secure Inside the access compartment, follow Just below the crimp connector, cut Plug both the blower Check all safety devices to make sure they Unplug the water heater from wall outlet Mitw -12 / -15 Series Place template on top of water heater in correct orientation TTW1 Universal Service Replacement Blower Secure Cover Screws Blower screws TTW1 Universal Service Replacement Blower Do not over tighten 2 screws attaching Tighten 2 screws on junction Box to secure cover Operation could occur if these devices are not M1TW60T*FCX TTW1 Universal Service Replacement Blower TTW1 Universal Service Replacement Blower Secure Cover screws Boot back Place Secure 3 blower screws Step If the new adapter is used, remove the old