GE 263, 268 manual Ultramax Series Controller Troubleshooting, Problem Possible Cause Solution

Page 39

Troubleshooting

Ultramax Series Controller Troubleshooting

Problem

Possible Cause

Solution

 

 

 

 

 

 

ERR 1 is displayed.

Program settings have been corrupted.

Press any key and reset model number.

 

 

 

ERR 3 is displayed.

Controller does not know the position of

Wait for two minutes for the controller to

 

the camshaft. Camshaft should be

return to Home position. The hourglass

 

rotating to find Home position.

should be flashing on the display

 

 

indicating the motor is running.

 

 

 

 

Camshaft is not turning during ERR 3

Check that motor is connected.

 

display.

Verify that motor wire harness is

 

 

connected to motor and controller

 

 

module.

 

 

Verify that optical sensor is connected

 

 

and in place.

 

 

Verify that motor gear has engaged cam

 

 

gear.

 

 

If everything is connected, try replacing

 

 

in this order:

 

 

—Wire harness

 

 

—Motor

 

 

—Optical sensor

 

 

—Controller

 

 

 

 

If camshaft is turning for more than five

Verify that optical sensor is in place and

 

minutes to find Home position:

connected to wire.

 

 

Verify that camshaft is connected

 

 

appropriately.

 

 

Verify that no dirt or rubbish is clogging

 

 

any of the cam slots.

 

 

If motor continues to rotate indefinitely,

 

 

replace the following components in this

 

 

order:

 

 

—Wire harness

 

 

—Motor

 

 

—Optical sensor

 

 

—Controller

 

 

 

Time of Day incorrect.

Power failure occurred.

Press SET to reset the time display.

 

 

 

Troubleshooting

39

 

Rev A

Image 39 Contents
Operations Manual Table of Contents Icons That Appear In This Manual Introduction How To Use This ManualGeneral Warnings And Safety Information ElectricalMechanical General System Operation Cycle Functions Cycle Water Flows Equipment Installation Valve Layout Ultramax Controller Control LayoutOutdoor Locations Location SelectionLocation Selection Rev a Water Line Connection Water Line Connection Rev a Drain Line Connection Drain LineNot used with 3-cycle filter system Regenerant Line ConnectionOverflow Line Connection Overflow Line Connection Rev a AC Adapter Input Application Part Number Electrical ConnectionVAC AC Adapters Controller LocationValve Camshaft 25% Sodium Hypochlorite Disinfection Of Water ConditionersValve Disc Operation Sodium or Calcium Hypochlorite ApplicationCalcium Hypochlorite Controller Memory Power Loss Memory RetentionUltramax Controller MotorDisplay Icons Programming Conventions Keypad ButtonsThings You Might Need to Know Setting Time of Day Programming OverviewLevel I Programming Setting Regeneration Time Setting Day of WeekFilter Operation Type Setting the Calendar OverrideLevel II Programming Conditioner Operation TypeSetting the Hardness conditioner only Setting Backwash Days 263 filter onlySetting the Salt Amount 268 softener only Setting Capacity Softener Default Capacity SettingViewing the Injector Type Setting Clock ModeSetting Units of Measure Adjusting the Cycle Times Conditioner Cycle TimesOperation Type Setting the Service IntervalSetting the Chlorine Generator/Salt Check conditioner only Total Water Used GAL X 100a Months Since SERVICEaLevel III Programming Peak Flow Rate GPMaPlacing Conditioner Into Operation Conditioner and Filter Start-UpFunction Display Text SET Action Key Duration DisplayRev a Performa Exploded View Part Code Description Qty Performa Parts ListTroubleshooting Ultramax Series Controller TroubleshootingProblem Possible Cause Solution System Troubleshooting Intermittent or Low water pressure Rev a Controller Reset UltraMax System Configurations