Argosy Research H-125 Series owner manual Refill Flow Control Assembly or Refill Port Plug

Page 37

Refill Flow Control Assembly or Refill Port Plug

To clean or replace the refill flow control, pull out the elbow-locking clip and then pull straight up on the elbow. Replace the elbow locking clip in the slot so that it is not misplaced. Twist to remove the white flow control re- tainer. The flow control can be removed by prying upward through the side slots of the retainer with a small flat blade screwdriver.

Chemically clean the flow control or the white flow control retainer using dilute sodium bisulfite or vinegar. Do not use a wire brush. If necessary, replace the flow control, o- ring on the flow control retainer, or the o-ring on the elbow.

Reseat the flow control so the rounded end is visible in the flow control. Reseat the white flow control retainer by pushing the retainer into the elbow until the o-ring seats. Remove locking clip, push down on elbow to reseat and insert locking clip.

Do not use Vaseline, oils, or other unacceptable lubricants on o-rings. A silicone lubricant may be used on the o-ring on the elbow or the white retainer.

Water Meter or Meter Plug

The water meter assembly is connected to the PC board by a wire. If the entire water meter assembly is to be replaced, remove the control valve cover and disconnect the power source and water meter plugs from the PC board. Unlatch the drive assembly and lean it in forward. Unthread the water meter wire from the side of the drive assembly and through the drive back plate. To reinstall, rethread the water meter through the drive back plate and side of the drive assembly. Reattach the drive assembly and the water meter and power plugs.

If no water meter is visible, then a plug is installed, not a water meter.

The water meter wire does not need to be removed from the PC board if the water meter is only being inspected and cleaned. To remove the water meter assembly, unscrew the meter cap on the left side of the control valve. Pliers may be used to unscrew the nut if necessary.

With the nut removed, a slot at the top of the water meter is visible. Twist a flat blade screwdriver in the slot be- tween the control valve body and the meter. When the meter is part way out it is easy to remove the water meter from the housing. Once the water meter is removed from the control valve body, gently pull forward on the turbine to remove it from the shaft.

Do not use a wire brush to clean the turbine. Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar. The turbine can be immersed in the chemical.

Do not immerse electronics. If the turbine is scored or damaged or the bearings on the turbine are worn, replace the turbine.

Do not lubricate the turbine shaft. The turbine shaft bear- ings are prelubricated. Do not use Vaseline, oils, or other unacceptable lubricants on the o-ring. A silicone lubricant may be used on the black o-ring.

Snap the turbine on the shaft and reinsert the water meter into the side slot. Hand tighten the nut. Do not use a pipe wrench to tighten nut.

Bypass Valve

The working parts of the bypass valve are the rotor as- semblies that are contained under the bypass valve caps. Before working on the rotors, make sure the system is de- pressurized. Turn the red arrow shaped handles towards the center of the bypass valve and back several times to ensure rotor is turning freely.

The nuts and caps are designed to be unscrewed or tightened by hand. If necessary a pliers can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten or loosen nuts or caps. Do not place screwdriver in slots on caps and/or tap with a hammer. To access the ro- tor, unscrew the cap and lift the cap, rotor and handle out as one unit. Twisting the unit as you pull it out will help to remove it more easily. There are three o-rings: one under the rotor cap, one on the rotor stem and the rotor seal. Replace worn o-rings. Clean rotor. Reinstall rotor.

When installing the red arrow handles be sure that:

1.The handle pointers are lined up with the control valve body arrows, and the rotor seal o-ring and retainer on both rotors face to the right when being viewed from the front of the control valve; or

2.Arrows point toward each other in the bypass position.

Since the handles can by pulled off, they could be ac- cidently reinstalled 180º from their correct orientation. To install the red arrow handles correctly, keep the handles pointed in the same direction as the arrows engraved on the control valve body while tightening the bypass valve caps.

After completing any valve maintenance, press and hold NEXT and REGEN buttons for 3 seconds or unplug power source jack (black wire) and plug back in. This resets the electronics and establishes the service piston position. The display should flash all wording, then flash the soft- ware version and reset the valve to the service position.

37

Image 37
Contents With HP Electronics Table of Contents On TimeRelay Job Specification SheetOperating Conditions Soft Water BasicsBypass valve Operation Pre-Installation Check ListInstallation Instructions 650 User displays/settings635 Programming635PM Installer DISPLAYS/SETTINGS20 GR SET Time of DAYSoftener setup Cycle time adjustments800 MIN SET 12000 MIN6000 MIN MIN300 MIN 001 MINSET Regengal Service ReminderReset Diagnostic Values Hold Diagnostics342 GAL Valve History 175 x1KBrine Reclaim Cycle Sequence800MIN EnabledOFF Water Softener Disinfection Water Softener Draining ProcedureMiscellaneous Cause Correction Trouble ShootingTrouble Shooting Problem Cause Relay troubleshootingDescription Qty H125 conditioner & salt keeper assembliesTank Assy Mineral Tank Distributor AssyDrawing no Order no Description Quantity Front Cover and Drive AssemblyInjector CAP, Injector SCREEN, INJECTOR, Plug and O-RING Spacer Stack AssemblyProper flow Drain line Drain line 3/4Bypass valve Water meter and meter plugInstallation fitting assemblies Wrench Flow Diagrams Service and Backwash Flow Diagrams Downflow Flow Diagrams Rinse and Fill Factory Regeneration Settings H125 SpecificationsProgramming options General specificationsResults Reserve capacity estimate based on history of water usageService Instructions Compliance Table Spacer Stack AssemblyRefill Flow Control Assembly or Refill Port Plug Page Page H125 Series Water Softeners Limited warranty