Rosemount 1154

Section 2

Installation

OVERVIEW

GENERAL CONSIDERATIONS

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1 Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . page 2-2 Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4 Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-6

This section contains information and instructions regarding the following installation-related information:

General Considerations

Mechanical Considerations Process Connections Conduit

Electrical Considerations

Installation Procedures Mechanical Electrical

The quality and accuracy of flow, level, or pressure measurement depends largely on the proper installation of the transmitter and its associated impulse piping and valves. For flow measurement, proper installation of the primary measuring element is also critical to the accuracy of the measurement. Transmitter installation should minimize the effects of temperature gradients and temperature fluctuations, and avoid vibration and shock during normal operation. Take care when designing the measurement to minimize the error caused by incorrect installation. The ambient temperature of the transmitter environment affects the qualified life of the transmitter (see Figure 2-1).

www.rosemountnuclear.com

Image 13
Contents Reference Manual RosemountImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Changes From June 1999 to January Revision StatusNew Old Changes Rosemount Table of Contents Specifications Reference Data Maintenance TroubleshootingSection TOC-3 TOC-4 Overview About the Transmitter Section IntroductionRosemount Overview General Considerations Section InstallationProcess Connections Mechanical ConsiderationsRosemount Electrical Considerations ConduitTransmitter Wiring Connections Procedures InstallationMechanical Range Code Pressure DimensionElectrical Liquid ServiceTransmitter Terminal Block Rosemount Section Calibration Span Adjustment Zero AdjustmentOverview Calibration Zero and Span Adjustment Calibration ProceduresZero and Span Adjustment Screws Linearity Adjustment Linearity and Damping Adjustment Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Overview Transmitter Operation Section OperationΔ-Cell Demodulator Linearity AdjustmentFV Iref Overview Maintenance TroubleshootingTest Terminals Board Checkout Safety MessagesSensing Module Checkout Process Flange Removal Disassembly ProcedurePart Description Rosemount 1154 Parts ListReassembly Procedure Rosemount Process Flange Reassembly Symptom Potential Source Corrective Action Post Assembly TestsOn Next Check for adequate voltage to the transmitter Nuclear Specifications Specifications and Reference DataPerformance Specifications Range Code Overpressure Effect Range Code Static Pressure Zero Effect Functional SpecificationsRange Code Response Time 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPa Range Code Pressure RangesRange Code Overpressure Limit Physical SpecificationsRosemount Ordering Information Rosemount 1154DP 1154HP 1154GP Part Description Order No Rosemount 1154DP, 1154HP, and 1154GP Spare PartsFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤