Rosemount 1154
Reference Manual
Post DBE Operation
Accuracy at reference conditions shall be within ±2.5% of upper range limit (±3.75% for Range Code 0) for one year following DBE.
Quality Assurance Program
In accordance with
Nuclear Cleaning
To 1 ppm maximum chloride content
Hydrostatic Testing
To 150% of maximum working pressure or 2,000 psi (13.8 MPA), whichever is greater
Traceability
In accordance with
Qualified Life
The transmitter qualified life is dependent on continuous ambient temperature at the installation site (see Figure
Figure 6-1. Qualified Life vs. Ambient Temperature.
Module |
Qualified Life |
Electronics |
Qualified Life |
Time (Years) |
Temperature (°F) |
PERFORMANCE SPECIFICATIONS
Based on
Accuracy
±0.25% of calibrated span; includes combined effects of linearity, hysteresis, and repeatability
Dead Band
None