Reference Manual
Rosemount 1154
Transmitters with Flange Options A, D, H, J, L, or M are shipped with Swagelok fittings for process connections. Included are front ferrule, rear ferrule, and nut. Ensure that the fittings are placed on the tubing with the orientation and relative position shown in Detail A, Figure
The connections can be loosened and
Fittings Catalog
“Gaugable Tube Fittings and Adapter Fittings” www.swagelok.com
If the drain/vent valves must be opened to bleed process lines, torque them to 7.5
Proper location of the transmitter with respect to the process tubing depends on various process parameters. When determining the best location, consider the following:
•Keep hot or corrosive fluids from contacting the transmitter.
•Prevent sediment from depositing in the impulse tubing.
•Ambient temperature gradients and fluctuations can result in erroneous transmitter readings.
•Keep impulse tubing as short as possible.
•For differential transmitters, balance the liquid head on both legs of the impulse tubing.
•For liquid flow or pressure measurements, make taps on the side of the line to avoid sediment deposits, and mount the transmitter beside or below the taps so gases vent into the process line (see Figure
•For gas flow or pressure measurements, make taps on the top or side of the line and mount the transmitter beside or above the taps so liquid drains into the process line (see Figure
•For steam flow or pressure measurements, make taps on the side of the line, and mount the transmitter below the taps so the impulse tubing stays filled with condensate (See Figure
•For steam service, fill the lines with water to prevent steam from contacting the transmitter. Condensate chambers are not necessary since the volumetric displacement of the transmitter
is negligible.