Emerson Complete Reference Manual for the Rosemount 1154 Transmitter

Page 15

Reference Manual

00809-0100-4514, Rev BA January 2008

Rosemount 1154

Transmitters with Flange Options A, D, H, J, L, or M are shipped with Swagelok fittings for process connections. Included are front ferrule, rear ferrule, and nut. Ensure that the fittings are placed on the tubing with the orientation and relative position shown in Detail A, Figure 2-5 on page 2-7.Process tubing used is 3/8-inch outside diameter, and of suitable thickness for the pressure involved.

The connections can be loosened and re-tightened 20-30 times without compromising the leak proof seal. To reconnect, insert the tubing with pre-swaged ferrules into the fitting until the front ferrule sits in the fitting. Tighten the nut by hand, then rotate one-quarter turn more or to the original one-and-one-quarter tight position. Then snug the nut slightly with a wrench. For more information regarding the use of Swagelok tube fittings, refer to:

Fittings Catalog MS-01-140

“Gaugable Tube Fittings and Adapter Fittings” www.swagelok.com

If the drain/vent valves must be opened to bleed process lines, torque them to 7.5 ft-lb (10 N-m) when closing.

Proper location of the transmitter with respect to the process tubing depends on various process parameters. When determining the best location, consider the following:

Keep hot or corrosive fluids from contacting the transmitter.

Prevent sediment from depositing in the impulse tubing.

Ambient temperature gradients and fluctuations can result in erroneous transmitter readings.

Keep impulse tubing as short as possible.

For differential transmitters, balance the liquid head on both legs of the impulse tubing.

For liquid flow or pressure measurements, make taps on the side of the line to avoid sediment deposits, and mount the transmitter beside or below the taps so gases vent into the process line (see Figure 2-6 on page 2-8).

For gas flow or pressure measurements, make taps on the top or side of the line and mount the transmitter beside or above the taps so liquid drains into the process line (see Figure 2-6 on page 2-8).

For steam flow or pressure measurements, make taps on the side of the line, and mount the transmitter below the taps so the impulse tubing stays filled with condensate (See Figure 2-6 on page 2-8).

For steam service, fill the lines with water to prevent steam from contacting the transmitter. Condensate chambers are not necessary since the volumetric displacement of the transmitter

is negligible.

2-3

Image 15
Contents Reference Manual RosemountImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Revision Status Changes From June 1999 to JanuaryNew Old Changes Rosemount Table of Contents Maintenance Troubleshooting Specifications Reference DataSection TOC-3 TOC-4 Overview About the Transmitter Section IntroductionRosemount Overview General Considerations Section InstallationProcess Connections Mechanical ConsiderationsRosemount Electrical Considerations ConduitTransmitter Wiring Connections Installation ProceduresMechanical Range Code Pressure DimensionElectrical Liquid ServiceTransmitter Terminal Block Rosemount Span Adjustment Zero Adjustment Section CalibrationOverview Calibration Zero and Span Adjustment Calibration ProceduresZero and Span Adjustment Screws Linearity Adjustment Linearity and Damping Adjustment Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Overview Transmitter Operation Section OperationΔ-Cell Demodulator Linearity AdjustmentFV Iref Overview Maintenance TroubleshootingTest Terminals Board Checkout Safety MessagesSensing Module Checkout Process Flange Removal Disassembly ProcedurePart Description Rosemount 1154 Parts ListReassembly Procedure Rosemount Process Flange Reassembly Post Assembly Tests Symptom Potential Source Corrective ActionOn Next Check for adequate voltage to the transmitter Nuclear Specifications Specifications and Reference DataPerformance Specifications Range Code Overpressure Effect Functional Specifications Range Code Static Pressure Zero EffectRange Code Response Time 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPa Range Code Pressure RangesRange Code Overpressure Limit Physical SpecificationsRosemount Ordering Information Rosemount 1154DP 1154HP 1154GP Part Description Order No Rosemount 1154DP, 1154HP, and 1154GP Spare PartsFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤