Emerson 1154 manual Post Assembly Tests, Symptom Potential Source Corrective Action, On Next

Page 43

Reference Manual

00809-0100-4514, Rev BA January 2008

Rosemount 1154

POST ASSEMBLY TESTS

1.Conduct hydrostatic testing to 150% of maximum working pressure or 2,000 psi, whichever is greater.

2.Calibrate the transmitter per the calibration section of this manual.

3.Conduct nuclear cleaning to 1 ppm chloride content of transmitter “wetted parts.”

Table 5-2. Torque References.

ITEM(S) TO BE TORQUED

TORQUE VALUE

TOLERANCE

 

 

 

Bracket to Mounting Panel Bolts

19 ft-lb (26 N-m)

±1 ft-lb (1 N-m)

 

 

 

Transmitter to Bracket Bolts

21 ft-lb (29 N-m)

±1 ft-lb (1 N-m)

 

 

 

Swagelok Process Fittings

See Installation Instructions

 

 

 

Drain/Vent Valves

7.5 ft-lb (10 N-m)

±0.5 ft-lb (0.7 N-m)

 

 

 

Covers

16.5 ft-lb (22.4 N-m)

±1 ft-lb (1 N-m)

 

 

 

Module Neck Lock Nut

35 ft-lb (48 N-m)

±1 ft-lb (1 N-m)

 

 

 

Conduit Fitting

4 to 7 turns or a minimum of 12.5 ft-lb (16.9

±1 ft-lb (1 N-m)

 

N-m)

 

 

 

 

Flange Bolts

See Process Flange Reassembly

 

 

 

Terminal Block Screws

5 in-lb (0.6 N-m) or hand tight

±1 in-lb (0.1 N-m)

 

 

 

Amplifier Board Screws

Nominal 10 in-lb (1.1 N-m)

 

 

 

Table 5-3. Troubleshooting.

Symptom

Potential Source

Corrective Action

 

 

 

High Output

Primary Element

Check for restrictions at primary element, improper installation or poor condition. Note any

 

 

changes in process fluid properties that may affect output.

 

 

 

 

Impulse Piping

Check for leaks or blockage.

 

 

Ensure blocking locking valves are fully open.

 

 

Check for entrapped gas in liquid lines, or liquid in dry lines.

 

 

Ensure that density of fluid in impulse line is unchanged.

 

 

Check for sediment in transmitter process flanges.

 

 

 

 

Transmitter

Make sure that post connectors and the sensor connections are clean. If the electronics are

 

Electronics

still suspect, substitute new electronics.

 

 

 

 

Transmitter

Determine faulty circuit board by trying spare boards. Replace faulty circuit board.

 

Electronics Failure

 

 

 

 

 

Sensing Module

See Sensing Module Checkout section. The sensing element is not field repairable and must

 

 

be replaced if found to be defective. See “Disassembly Procedure” for instructions on

 

 

disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill fluid

 

 

loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.

 

 

 

 

Power Supply

Check the power supply output voltage at the transmitter.

 

 

 

 

 

Continued on Next Page

 

 

 

 

 

 

5-9

Image 43
Contents Reference Manual RosemountImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Changes From June 1999 to January Revision StatusNew Old Changes Rosemount Table of Contents Specifications Reference Data Maintenance TroubleshootingSection TOC-3 TOC-4 Overview About the Transmitter Section IntroductionRosemount Overview General Considerations Section InstallationProcess Connections Mechanical ConsiderationsRosemount Electrical Considerations ConduitTransmitter Wiring Connections Procedures InstallationMechanical Range Code Pressure DimensionElectrical Liquid ServiceTransmitter Terminal Block Rosemount Section Calibration Span Adjustment Zero AdjustmentOverview Calibration Zero and Span Adjustment Calibration ProceduresZero and Span Adjustment Screws Linearity Adjustment Linearity and Damping Adjustment Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Overview Transmitter Operation Section OperationΔ-Cell Demodulator Linearity AdjustmentFV Iref Overview Maintenance TroubleshootingTest Terminals Board Checkout Safety MessagesSensing Module Checkout Process Flange Removal Disassembly ProcedurePart Description Rosemount 1154 Parts ListReassembly Procedure Rosemount Process Flange Reassembly Symptom Potential Source Corrective Action Post Assembly TestsOn Next Check for adequate voltage to the transmitter Nuclear Specifications Specifications and Reference DataPerformance Specifications Range Code Overpressure Effect Range Code Static Pressure Zero Effect Functional SpecificationsRange Code Response Time 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPa Range Code Pressure RangesRange Code Overpressure Limit Physical SpecificationsRosemount Ordering Information Rosemount 1154DP 1154HP 1154GP Part Description Order No Rosemount 1154DP, 1154HP, and 1154GP Spare PartsFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤