Emerson 1154, 00809-0100-4514 manual Section Operation, Overview Transmitter Operation

Page 31

Reference Manual

00809-0100-4514, Rev BA January 2008

Rosemount 1154

Section 4

Operation

OVERVIEW

TRANSMITTER OPERATION

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1 Transmitter Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1The δ-Cell Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3 Demodulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3 Linearity Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-3 Oscillator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-4 Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-4 Zero and Span Adjustments . . . . . . . . . . . . . . . . . . . . . . . page 4-4 Current Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-4 Current Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-4 Reverse Polarity Protection . . . . . . . . . . . . . . . . . . . . . . . . page 4-4

This section provides brief descriptions of basic transmitter operations in the following order:

Transmitter Operation

The ￿-CellSensor

Demodulator

Linearity Adjustment

Oscillator

Voltage Regulator

Zero and Span Adjustments

Current Control

Current Limit

Reverse Polarity Protection

The block diagram in Figure 4-2 on page 4-3illustrates the operation of the transmitter.

The Rosemount 1154 Alphaline Pressure Transmitters have a variable capacitance sensing element, the δ-Cell (Figure 4-1 on page 4-2). Differential capacitance between the sensing diaphragm and the capacitor plates is converted electronically to a 2-wire 4–20 mA dc signal.

P = K

 

⎛ C2

C1

1

--------------------

 

C1

+ C2

Where:

Pis the process pressure.

www.rosemountnuclear.com

Image 31
Contents Reference Manual RosemountImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Changes From June 1999 to January Revision StatusNew Old Changes Rosemount Table of Contents Specifications Reference Data Maintenance TroubleshootingSection TOC-3 TOC-4 Overview About the Transmitter Section IntroductionRosemount Overview General Considerations Section InstallationProcess Connections Mechanical ConsiderationsRosemount Electrical Considerations ConduitTransmitter Wiring Connections Procedures InstallationMechanical Range Code Pressure DimensionElectrical Liquid ServiceTransmitter Terminal Block Rosemount Section Calibration Span Adjustment Zero AdjustmentOverview Calibration Zero and Span Adjustment Calibration ProceduresZero and Span Adjustment Screws Linearity Adjustment Linearity and Damping Adjustment Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Overview Transmitter Operation Section OperationΔ-Cell Demodulator Linearity AdjustmentFV Iref Overview Maintenance TroubleshootingTest Terminals Board Checkout Safety MessagesSensing Module Checkout Process Flange Removal Disassembly ProcedurePart Description Rosemount 1154 Parts ListReassembly Procedure Rosemount Process Flange Reassembly Symptom Potential Source Corrective Action Post Assembly TestsOn Next Check for adequate voltage to the transmitter Nuclear Specifications Specifications and Reference DataPerformance Specifications Range Code Overpressure Effect Range Code Static Pressure Zero Effect Functional SpecificationsRange Code Response Time 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPa Range Code Pressure RangesRange Code Overpressure Limit Physical SpecificationsRosemount Ordering Information Rosemount 1154DP 1154HP 1154GP Part Description Order No Rosemount 1154DP, 1154HP, and 1154GP Spare PartsFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤