Rosemount 1154
Reference Manual
Symptom | Potential Source | Corrective Action |
|
|
|
Low Output or | Primary Element | Check for restrictions at primary element, improper installation or poor condition. |
No Output |
| Note any changes in process fluid properties that may affect output. |
|
|
|
| Loop Wiring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Do not use over 100 volts to check the loop, or damage to the transmitter |
| |
|
| electronics may result. |
| |
|
|
|
|
|
|
| Check for adequate voltage to the transmitter. | ||
|
| Check the milliamp rating of the power supply against the total current being drawn for all | ||
|
| transmitters being powered. | ||
|
| Check for shorts and multiple grounds. | ||
|
| Check for proper polarity at the signal terminal. | ||
|
| Check loop impedance. | ||
|
| Check wire insulation to detect possible shorts to ground. | ||
|
|
|
|
|
| Impulse Piping | Ensure that the pressure connection is correct. | ||
|
| Check for leaks or blockage. | ||
|
| Check for entrapped gas in liquid lines. | ||
|
| Check for sediment in the transmitter process flange. | ||
|
| Ensure that blocking valves are fully open and that bypass valves are tightly closed. | ||
|
| Ensure that density of the fluid in the impulse piping is unchanged. | ||
|
|
|
|
|
| Transmitter | Ensure that calibration adjustments are in allowable range. | ||
| Electronics | Check for shorts in sensor leads. | ||
| Connections | Make sure post connectors are clean, and check the sensor connections. | ||
|
| If the electronics are still suspect, substitute new electronics. | ||
|
|
|
|
|
| Test Diode Failure | Replace electronics housing. | ||
|
|
|
|
|
| Transmitter | Determine faulty circuit board by trying spare boards. Replace faulty circuit board. | ||
| Electronics Failure |
|
|
|
|
|
|
|
|
| Sensing Module | NOTE: See Sensing Module Checkout section. The sensing element is not field repairable | ||
|
| and must be replaced if found to be defective. See “Disassembly Procedure” for instructions | ||
|
| on disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill | ||
|
| fluid loss, and contact Rosemount Nuclear Instruments, Inc. at (952) | ||
|
|
|
|
|
| Power Supply | Check the power supply output voltage at the transmitter. | ||
|
|
|
|
|
Erratic Output | Loop Wiring |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Do not use over 100 volts to check the loop, or damage to the transmitter | |
| electronics may result. | |
|
|
|
| Check for inadequate voltage to the transmitter. | |
| Check for intermittent shorts, open circuits, or multiple grounds. | |
|
|
|
Impulse Piping and | Check for entrapped gas in liquid lines, or liquid in dry lines. | |
Process |
|
|
Connections |
|
|
|
|
|
Transmitter | Check for intermittent shorts or open circuits. | |
Electronics | Make sure that bayonet and sensor connectors are clean and properly connected. | |
|
|
|
Transmitter | Determine faulty circuit boards by trying spare boards. Replace faulty circuit board. | |
Electronics Failure |
|
|
|
|
|
Power Supply | Check power supply output voltage. |