Emerson 00809-0100-4514, 1154 manual Check for adequate voltage to the transmitter

Page 44

Rosemount 1154

Reference Manual

00809-0100-4514, Rev BA January 2008

Symptom

Potential Source

Corrective Action

 

 

 

Low Output or

Primary Element

Check for restrictions at primary element, improper installation or poor condition.

No Output

 

Note any changes in process fluid properties that may affect output.

 

 

 

 

Loop Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use over 100 volts to check the loop, or damage to the transmitter

 

 

 

electronics may result.

 

 

 

 

 

 

 

 

Check for adequate voltage to the transmitter.

 

 

Check the milliamp rating of the power supply against the total current being drawn for all

 

 

transmitters being powered.

 

 

Check for shorts and multiple grounds.

 

 

Check for proper polarity at the signal terminal.

 

 

Check loop impedance.

 

 

Check wire insulation to detect possible shorts to ground.

 

 

 

 

 

 

Impulse Piping

Ensure that the pressure connection is correct.

 

 

Check for leaks or blockage.

 

 

Check for entrapped gas in liquid lines.

 

 

Check for sediment in the transmitter process flange.

 

 

Ensure that blocking valves are fully open and that bypass valves are tightly closed.

 

 

Ensure that density of the fluid in the impulse piping is unchanged.

 

 

 

 

 

 

Transmitter

Ensure that calibration adjustments are in allowable range.

 

Electronics

Check for shorts in sensor leads.

 

Connections

Make sure post connectors are clean, and check the sensor connections.

 

 

If the electronics are still suspect, substitute new electronics.

 

 

 

 

 

 

Test Diode Failure

Replace electronics housing.

 

 

 

 

 

 

Transmitter

Determine faulty circuit board by trying spare boards. Replace faulty circuit board.

 

Electronics Failure

 

 

 

 

 

 

 

 

 

Sensing Module

NOTE: See Sensing Module Checkout section. The sensing element is not field repairable

 

 

and must be replaced if found to be defective. See “Disassembly Procedure” for instructions

 

 

on disassembly. Check for obvious defects, such as a punctured isolating diaphragm or fill

 

 

fluid loss, and contact Rosemount Nuclear Instruments, Inc. at (952) 949-5210.

 

 

 

 

 

 

Power Supply

Check the power supply output voltage at the transmitter.

 

 

 

 

 

Erratic Output

Loop Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use over 100 volts to check the loop, or damage to the transmitter

 

electronics may result.

 

 

 

 

Check for inadequate voltage to the transmitter.

 

Check for intermittent shorts, open circuits, or multiple grounds.

 

 

 

Impulse Piping and

Check for entrapped gas in liquid lines, or liquid in dry lines.

Process

 

 

Connections

 

 

 

 

 

Transmitter

Check for intermittent shorts or open circuits.

Electronics

Make sure that bayonet and sensor connectors are clean and properly connected.

 

 

 

Transmitter

Determine faulty circuit boards by trying spare boards. Replace faulty circuit board.

Electronics Failure

 

 

 

 

 

Power Supply

Check power supply output voltage.

5-10

Image 44
Contents Rosemount Reference ManualImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material New Old Changes Revision StatusChanges From June 1999 to January Rosemount Table of Contents Section Maintenance TroubleshootingSpecifications Reference Data TOC-3 TOC-4 Section Introduction Overview About the TransmitterRosemount Section Installation Overview General ConsiderationsMechanical Considerations Process ConnectionsRosemount Conduit Electrical ConsiderationsTransmitter Wiring Connections Mechanical InstallationProcedures Pressure Dimension Range CodeLiquid Service ElectricalTransmitter Terminal Block Rosemount Overview Calibration Span Adjustment Zero AdjustmentSection Calibration Calibration Procedures Zero and Span AdjustmentZero and Span Adjustment Screws Linearity Adjustment Damping Adjustment Linearity and Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Section Operation Overview Transmitter OperationΔ-Cell Linearity Adjustment DemodulatorFV Iref Maintenance Troubleshooting OverviewSafety Messages Test Terminals Board CheckoutSensing Module Checkout Disassembly Procedure Process Flange RemovalRosemount 1154 Parts List Part DescriptionReassembly Procedure Rosemount Process Flange Reassembly On Next Post Assembly TestsSymptom Potential Source Corrective Action Check for adequate voltage to the transmitter Specifications and Reference Data Nuclear SpecificationsPerformance Specifications Range Code Overpressure Effect Range Code Response Time Functional SpecificationsRange Code Static Pressure Zero Effect Range Code Pressure Ranges 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPaPhysical Specifications Range Code Overpressure LimitRosemount Ordering Information Rosemount 1154DP, 1154HP, and 1154GP Spare Parts Rosemount 1154DP 1154HP 1154GP Part Description Order NoFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤