Emerson 00809-0100-4514, 1154 manual Calibration Procedures, Zero and Span Adjustment

Page 24

Rosemount 1154

Reference Manual

00809-0100-4514, Rev BA January 2008

Figure 3-1. Zero Adjustment Range.

 

 

 

 

 

 

20

 

 

600% Zero Elevation

 

Output

 

 

 

(mA)

 

 

 

 

 

 

 

 

 

 

 

 

4

–150

–125

–100 –75

–50

–25

0

25

Pressure (inH2O)

600% Zero Elevation

20

Output (mA)

4

0 25

Pressure (inH2O)

No Zero Elevation or Suppression

 

20

 

 

 

 

 

 

Output

 

 

 

 

 

 

 

(mA)

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

25

50

75

100

125

150

Pressure (inH2O)

500% Zero Suppression

Graphs based on a Range Code 4 (0–25 to 0–150 inH2O) Rosemount 1154 with a calibrated span of 25 inH2O.

CALIBRATION PROCEDURES

Zero and Span Adjustment

NOTE

The Rosemount 1154 Pressure Transmitter contains electronic circuit boards which may be static sensitive.

NOTE

Covers need not be removed for zero and span adjustment.

The zero and span adjustment screws are accessible externally. They are located behind the nameplate on the side of the electronics housing (see Figure 3-2 on page 3-3). The transmitter output increases with clockwise rotation of the adjustment screws.

The zero adjustment screw has very little effect on the span. The span adjustment, however, does affect the zero. The effect of interaction is more apparent with suppression or elevation. The span adjustment changes the zero output and the full-scale output by approximately the same percentage. Therefore, it is best to calibrate the transmitter from zero to the desired span and finish the calibration by adjusting the zero screw to achieve the desired elevation or suppression.

3-2

Image 24
Contents Rosemount Reference ManualImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Revision Status Changes From June 1999 to JanuaryNew Old Changes Rosemount Table of Contents Maintenance Troubleshooting Specifications Reference DataSection TOC-3 TOC-4 Section Introduction Overview About the TransmitterRosemount Section Installation Overview General ConsiderationsMechanical Considerations Process ConnectionsRosemount Conduit Electrical ConsiderationsTransmitter Wiring Connections Installation ProceduresMechanical Pressure Dimension Range CodeLiquid Service ElectricalTransmitter Terminal Block Rosemount Span Adjustment Zero Adjustment Section CalibrationOverview Calibration Calibration Procedures Zero and Span AdjustmentZero and Span Adjustment Screws Linearity Adjustment Damping Adjustment Linearity and Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Section Operation Overview Transmitter OperationΔ-Cell Linearity Adjustment DemodulatorFV Iref Maintenance Troubleshooting OverviewSafety Messages Test Terminals Board CheckoutSensing Module Checkout Disassembly Procedure Process Flange RemovalRosemount 1154 Parts List Part DescriptionReassembly Procedure Rosemount Process Flange Reassembly Post Assembly Tests Symptom Potential Source Corrective ActionOn Next Check for adequate voltage to the transmitter Specifications and Reference Data Nuclear SpecificationsPerformance Specifications Range Code Overpressure Effect Functional Specifications Range Code Static Pressure Zero EffectRange Code Response Time Range Code Pressure Ranges 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPaPhysical Specifications Range Code Overpressure LimitRosemount Ordering Information Rosemount 1154DP, 1154HP, and 1154GP Spare Parts Rosemount 1154DP 1154HP 1154GP Part Description Order NoFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤