Emerson 00809-0100-4514, 1154 manual Rosemount

Page 30

Rosemount 1154

Reference Manual

00809-0100-4514, Rev BA January 2008

Equalize pressure to both process connections, and turn the zero adjustment until the ideal output at zero differential input is observed. Do not readjust the span potentiometer.

If the transmitter does not include zero differential pressure within its calibrated span, the zero effect or zero correction can be determined before the unit is suppressed or elevated to eliminate the zero effect after correcting for the span effect.

The following procedure illustrates how to eliminate the zero effect for a non-zero differential pressure calibration. The example uses a Range Code 5, calibrated from 100 to 500 inH2O, with 1,200 psi static line pressure.

1.Using standard calibration procedures, calibrate the unit to the required span, with the 4 mA or zero point corresponding to zero differential pressure:

4 mA at 0 inH2O and 20 mA at 400 inH2O

2.Apply static pressure to both high and low process connections with zero differential pressure across the transmitter, and note the zero correction (zero shift). For example, if the output reads 4.006 mA, the zero correction is calculated as:

4.00 mA – 4.006 mA = –0.006 mA

Note the sign associated with this correction, as this result is added when determining the final, ideal transmitter output.

3.Remove static pressure and correct for the span effect as outlined in the span correction procedure. Calibrate the unit to the calculated output values. If, for example, the span correction procedure yielded

4.029 mA and 20.144 mA, calibrate the unit for:

4.029 mA at 100 inH2O

20.144 mA at 500 inH2O

4.Add the zero correction (–0.006 mA), found in step 2, to the ideal zero point value calculated in step 3.

4.029 mA + (–0.006 mA) = 4.023 mA

5.To eliminate the zero effect, readjust the zero potentiometer so the output reads the ideal zero point calculated in step 4 (do not readjust the span potentiometer). Note that all the calibration points will shift the same amount toward the correct reading. The example output is now 4.023 mA at 100 inH2O.

The transmitter output is now 4–20 mA over its calibrated span when the unit is operated at 1,200 psi static line pressure.

3-8

Image 30
Contents Rosemount Reference ManualImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Revision Status Changes From June 1999 to JanuaryNew Old Changes Rosemount Table of Contents Maintenance Troubleshooting Specifications Reference DataSection TOC-3 TOC-4 Section Introduction Overview About the TransmitterRosemount Section Installation Overview General ConsiderationsMechanical Considerations Process ConnectionsRosemount Conduit Electrical ConsiderationsTransmitter Wiring Connections Installation ProceduresMechanical Pressure Dimension Range CodeLiquid Service ElectricalTransmitter Terminal Block Rosemount Span Adjustment Zero Adjustment Section CalibrationOverview Calibration Calibration Procedures Zero and Span AdjustmentZero and Span Adjustment Screws Linearity Adjustment Damping Adjustment Linearity and Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Section Operation Overview Transmitter OperationΔ-Cell Linearity Adjustment DemodulatorFV Iref Maintenance Troubleshooting OverviewSafety Messages Test Terminals Board CheckoutSensing Module Checkout Disassembly Procedure Process Flange RemovalRosemount 1154 Parts List Part DescriptionReassembly Procedure Rosemount Process Flange Reassembly Post Assembly Tests Symptom Potential Source Corrective ActionOn Next Check for adequate voltage to the transmitter Specifications and Reference Data Nuclear SpecificationsPerformance Specifications Range Code Overpressure Effect Functional Specifications Range Code Static Pressure Zero EffectRange Code Response Time Range Code Pressure Ranges 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPaPhysical Specifications Range Code Overpressure LimitRosemount Ordering Information Rosemount 1154DP, 1154HP, and 1154GP Spare Parts Rosemount 1154DP 1154HP 1154GP Part Description Order NoFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤