Emerson 00809-0100-4514, 1154 Functional Specifications, Range Code Static Pressure Zero Effect

Page 48

Rosemount 1154

Reference Manual

00809-0100-4514, Rev BA January 2008

Static Pressure Zero Effect

Rosemount 1154DP:

Per 1,000 psi (6.89 MPa):

Range Code

Static Pressure Zero Effect

 

 

4, 5

±0.2% of upper range limit

6–8

±0.5% of upper range limit

 

 

FUNCTIONAL SPECIFICATIONS

Rosemount 1154HP:

Per 1,000 psi (6.89 MPa):

Range Code

Static Pressure Zero Effect

 

 

All Ranges

±0.66% of upper range limit

 

 

Static Pressure Span Effect

Effect is systematic and can be calibrated out for a particular pressure before installation. Correction uncertainty is ±0.5% of input

reading/1,000 psi (6.89 MPa).

Power Supply Effect

Less than 0.005% of output span/volt

Load Effect

No load effect other than the change in voltage supplied to the transmitter

Mounting Position Effect

No span effect; zero shift of up to 1.5 inH2O (372 Pa) which can be calibrated out

Response Time

Fixed time constant (63%) at 100 °F (37.8 °C) as follows:

Range Code

Response Time

 

 

4

0.5 seconds or less

all others

0.2 seconds or less

 

 

Adjustable damping is available through a special

N option.

Service

Liquid, gas, or vapor

Output

4–20 mA dc

Power Supply

Design limits are as shown in Figure 2-3 on page 2-5. See qualification report D8400102 for additional detail.

6-4

Image 48
Contents Rosemount Reference ManualImportant Notice -- Errata Rosemount 1154 Alphaline Nuclear Pressure Transmitter Return of Material Revision Status Changes From June 1999 to JanuaryNew Old Changes Rosemount Table of Contents Maintenance Troubleshooting Specifications Reference DataSection TOC-3 TOC-4 Section Introduction Overview About the TransmitterRosemount Section Installation Overview General ConsiderationsMechanical Considerations Process ConnectionsRosemount Conduit Electrical ConsiderationsTransmitter Wiring Connections Installation ProceduresMechanical Pressure Dimension Range CodeLiquid Service ElectricalTransmitter Terminal Block Rosemount Span Adjustment Zero Adjustment Section CalibrationOverview Calibration Calibration Procedures Zero and Span AdjustmentZero and Span Adjustment Screws Linearity Adjustment Damping Adjustment Linearity and Damping AdjustmentRosemount Calculate zero adjustment correction in terms of pressure Rosemount Section Operation Overview Transmitter OperationΔ-Cell Linearity Adjustment DemodulatorFV Iref Maintenance Troubleshooting OverviewSafety Messages Test Terminals Board CheckoutSensing Module Checkout Disassembly Procedure Process Flange RemovalRosemount 1154 Parts List Part DescriptionReassembly Procedure Rosemount Process Flange Reassembly Post Assembly Tests Symptom Potential Source Corrective ActionOn Next Check for adequate voltage to the transmitter Specifications and Reference Data Nuclear SpecificationsPerformance Specifications Range Code Overpressure Effect Functional Specifications Range Code Static Pressure Zero EffectRange Code Response Time Range Code Pressure Ranges 25 to 0-150 inH2O 0-6.22 to 0-37.3 kPaPhysical Specifications Range Code Overpressure LimitRosemount Ordering Information Rosemount 1154DP, 1154HP, and 1154GP Spare Parts Rosemount 1154DP 1154HP 1154GP Part Description Order NoFor use with existing N0026 transmitter only Spare Parts Shelf Life Important Notice Rosemount Current Control Current Limit Index-2 Page ¢00809-XXXX-XXXX ¤