Emerson IFT9701 instruction manual Orientation and mounting, Temperature, humidity, and vibration

Page 14

Getting Started continued

Figure 2-1 Location of approvals tag

Hazardous area approvals tag

2.1.2Orientation and mounting

Orient the transmitter so wiring compartments and conduit openings are easily accessible.

To rotate the transmitter on the sensor manifold or the mounting bracket, use the four supplied mounting bolt assemblies. Each bolt assembly includes one M8 bolt, one lock washer, and one flat washer. Remove the bolt assemblies, rotate the transmitter, then reinstall the bolt assemblies to 12 ft-lb (16 N-m) of torque.

If the transmitter will be integrally mounted to a Micro Motion F-Series sensor, see the sensor product data sheet for transmitter and sensor dimensions, and see the instruction manual that was shipped with the sensor for information about flowmeter mounting and location.

If the transmitter will be remotely mounted, use the supplied bolt assemblies to attach the transmitter to the mounting bracket. Attach the bracket to a rigid, stable surface or instrument pole that will not transfer excessive vibration into the transmitter. See Chapter 3 for more information about remote mounting.

2.1.3Temperature, humidity, and vibration

Install the transmitter according to specified limits:

Ambient temperature

-without optional LCD: –22 to +131 °F (–30 to +55 °C)

-with optional LCD: 32 to 131 °F (0 to 55 °C)

Humidity: 5 to 95% non-condensing

Vibration: Meets IEC 68.2.6, 2 g

6

Model IFT9701 Transmitter Instruction Manual

Image 14
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page About this manual Safety Before You BeginFlowmeter components European installationsDefinitions Remotely mounted IFT9701 transmitter Page Hazardous area Safety, reliability, accessibilityGetting Started Temperature, humidity, and vibration Orientation and mountingVisibility of tags Transmitters approved for Atex ZoneJumper settings Compartment tags and lockout deviceFault output levels SecurityRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Connecting the transmitter to the sensor Cable typesTemperature ranges for jacket material Cable selection guidelinesGuidelines for cable gland Wiring connections to sensorGuidelines for conduit Cable connections to sensors Sensor terminal designationsSensor wiring compartment and sensor wiring terminals Power Supply and Output Wiring Wiring guidelinesConnect power supply wiring Power supply wiring terminalsWire guidelines for DC power supply Connect output wiringMilliamp output Milliamp output performanceTypical Hart network wiring Milliamp output connected to Bell 202 multidrop networkCommunication tools connected to milliamp output Hart Communicator connectionsPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Flowmeter Startup Customer serviceStartup procedures ZeroingOperating mode Diagnostic LEDStartup mode InitializationZeroing procedure Flowmeter zeroingConfiguration, calibration, and characterization Diagnosing zero failureProcess measurement Page Configuration with a Hart Communicator Configuration overviewMeasurement units Configuration parametersHart tag Measurement units for mass and volume flow Mass flow unit Software label Volume flow unitFlow cutoff DampingFlow direction Effect of flow direction on outputs and totalizersRange values for milliamp output Pulse output scalingCalibration procedures Auto zeroFlow calibration procedure Diagnosing zeroing failureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Configuration window Flow panel Process variable measurementMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Output configuration Configuration window Analog Output panelConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel General guidelines TroubleshootingTransmitter diagnostic tools Normal conditions indicated by LED Fault outputsOptional LCD Power supply Conditions indicated by optional LCDPower supply connections WiringNormal resistance and voltage ranges for flowmeter circuits Over range and sensor failure conditionsTroubleshooting over range and sensor failure conditions Slug flowDigital diagnostic messages Transmitter failurePage Functional specifications Output signals Milliamp active IFT9701 SpecificationsPerformance specifications Pulse passivePower supply options 85 to 250 VAC Fault indicationOutput testing Current source Local display optional20 to 30 VDC Environmental limits Temperature OperatingProcess fluid vs. ambient temperature StorageDensity limits Humidity limitsVibration limits Environmental effects Ambient temperature effect on milliamp outputShipping weight Hazardous area classificationsPage Appendix B Hart Communicator Menu TreesHart Communicator Menu Trees Installing the Optional Display Appendix CInstalling the Optional Display Used equipment Return PolicyNew and unused equipment Page Index AtexHart Customer service Index Page 3100572