Emerson IFT9701 instruction manual Process variable measurement, Configuration window Flow panel

Page 55

Configuration with ProLink II Software continued

7.2.2Process variable measurement

To configure process variable measurement:

1.From the ProLink menu, click on Configuration.

2.In the Configuration window, click on the Flow tab. The Flow panel appers (as depicted in Figure 7-2).

Figure 7-2 Configuration window – Flow panel

3.To specify the flow measurement unit, open the Flow Units list box and select a flow unit. If you select a unit of mass flow, the transmitter will measure mass flow. If you select a unit of volume flow, the transmitter will measure volume flow. A list of available flow measurement units is provided in Table 7-1.

Flowmeter Startup

Configuration with Communicator

Configuration with ProLink II

Troubleshooting

Model IFT9701 Transmitter Instruction Manual

47

Image 55
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page Before You Begin About this manual SafetyDefinitions European installationsFlowmeter components Remotely mounted IFT9701 transmitter Page Getting Started Safety, reliability, accessibilityHazardous area Orientation and mounting Temperature, humidity, and vibrationTransmitters approved for Atex Zone Visibility of tagsCompartment tags and lockout device Jumper settingsSecurity Fault output levelsRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Cable types Connecting the transmitter to the sensorCable selection guidelines Temperature ranges for jacket materialGuidelines for conduit Wiring connections to sensorGuidelines for cable gland Sensor terminal designations Cable connections to sensorsSensor wiring compartment and sensor wiring terminals Wiring guidelines Power Supply and Output WiringPower supply wiring terminals Connect power supply wiringConnect output wiring Wire guidelines for DC power supplyMilliamp output performance Milliamp outputMilliamp output connected to Bell 202 multidrop network Typical Hart network wiringHart Communicator connections Communication tools connected to milliamp outputPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Zeroing Customer serviceStartup procedures Flowmeter StartupInitialization Diagnostic LEDStartup mode Operating modeFlowmeter zeroing Zeroing procedureDiagnosing zero failure Configuration, calibration, and characterizationProcess measurement Page Configuration overview Configuration with a Hart CommunicatorHart tag Configuration parametersMeasurement units Mass flow unit Software label Volume flow unit Measurement units for mass and volume flowDamping Flow cutoffEffect of flow direction on outputs and totalizers Flow directionPulse output scaling Range values for milliamp outputAuto zero Calibration proceduresDiagnosing zeroing failure Flow calibration procedureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Process variable measurement Configuration window Flow panelMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Configuration window Analog Output panel Output configurationConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel Transmitter diagnostic tools TroubleshootingGeneral guidelines Optional LCD Fault outputsNormal conditions indicated by LED Conditions indicated by optional LCD Power supplyWiring Power supply connectionsOver range and sensor failure conditions Normal resistance and voltage ranges for flowmeter circuitsSlug flow Troubleshooting over range and sensor failure conditionsTransmitter failure Digital diagnostic messagesPage Pulse passive IFT9701 SpecificationsPerformance specifications Functional specifications Output signals Milliamp activeLocal display optional Fault indicationOutput testing Current source Power supply options 85 to 250 VACStorage Environmental limits Temperature OperatingProcess fluid vs. ambient temperature 20 to 30 VDCVibration limits Humidity limitsDensity limits Hazardous area classifications Ambient temperature effect on milliamp outputShipping weight Environmental effectsPage Hart Communicator Menu Trees Appendix BHart Communicator Menu Trees Appendix C Installing the Optional DisplayInstalling the Optional Display New and unused equipment Return PolicyUsed equipment Page Atex IndexHart Customer service Index Page 3100572