Emerson IFT9701 instruction manual Connect power supply wiring, Power supply wiring terminals

Page 28

Power Supply and Output Wiring continued

4.3Connect power supply wiring

CAUTION

Incorrect voltage, or installation with power supply on, could cause transmitter damage or failure.

Match power supply voltage with voltage indicated on label in field wiring compartment.

Shut off power before installing transmitter.

Figure 4-1 shows the power supply wiring terminals.

Wiring terminals accommodate 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire. If the transmitter has a DC power supply, see Table 4-1 for wire length and size guidelines.

Connect power supply wiring to the power supply terminals.

A switch may be installed in the power supply line. For compliance with low-voltage directive 73/23/EEC, a switch in close proximity to the transmitter is required.

Do not install power cable in the same conduit or cable tray as flowmeter cable or output wiring.

The transmitter must be grounded with a maximum impedance of 1 ohm. Either the internal ground screw or external case ground screw may be used as required by local policy or code.

Figure 4-1 Power supply wiring terminals

AC

OR

DC

Power

transmitter

transmitter

 

terminals

 

 

 

N L

 

– +

 

85-250 VAC

 

20-30 VDC

Field wiring

 

compartment

Conduit opening for

power supply wiring

Sensor wiring compartment

External ground screw for power supply

Internal ground screw for power supply

If national standards are not in effect, adhere to these guidelines for grounding:

Use copper wire, 14 AWG (2,5 mm²) or larger wire size.

Keep all ground leads as short as possible, less than 1 ohm impedance.

Connect ground leads directly to earth, or follow plant standards.

For hazardous area installation in Europe, use standard EN 60079-14 as a guideline.

20

Model IFT9701 Transmitter Instruction Manual

Image 28
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page About this manual Safety Before You BeginDefinitions European installationsFlowmeter components Remotely mounted IFT9701 transmitter Page Getting Started Safety, reliability, accessibilityHazardous area Temperature, humidity, and vibration Orientation and mountingVisibility of tags Transmitters approved for Atex ZoneJumper settings Compartment tags and lockout deviceFault output levels SecurityRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Connecting the transmitter to the sensor Cable typesTemperature ranges for jacket material Cable selection guidelinesGuidelines for conduit Wiring connections to sensorGuidelines for cable gland Cable connections to sensors Sensor terminal designationsSensor wiring compartment and sensor wiring terminals Power Supply and Output Wiring Wiring guidelinesConnect power supply wiring Power supply wiring terminalsWire guidelines for DC power supply Connect output wiringMilliamp output Milliamp output performanceTypical Hart network wiring Milliamp output connected to Bell 202 multidrop networkCommunication tools connected to milliamp output Hart Communicator connectionsPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Customer service Startup proceduresFlowmeter Startup ZeroingDiagnostic LED Startup modeOperating mode InitializationZeroing procedure Flowmeter zeroingConfiguration, calibration, and characterization Diagnosing zero failureProcess measurement Page Configuration with a Hart Communicator Configuration overviewHart tag Configuration parametersMeasurement units Measurement units for mass and volume flow Mass flow unit Software label Volume flow unitFlow cutoff DampingFlow direction Effect of flow direction on outputs and totalizersRange values for milliamp output Pulse output scalingCalibration procedures Auto zeroFlow calibration procedure Diagnosing zeroing failureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Configuration window Flow panel Process variable measurementMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Output configuration Configuration window Analog Output panelConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel Transmitter diagnostic tools TroubleshootingGeneral guidelines Optional LCD Fault outputsNormal conditions indicated by LED Power supply Conditions indicated by optional LCDPower supply connections WiringNormal resistance and voltage ranges for flowmeter circuits Over range and sensor failure conditionsTroubleshooting over range and sensor failure conditions Slug flowDigital diagnostic messages Transmitter failurePage IFT9701 Specifications Performance specificationsFunctional specifications Output signals Milliamp active Pulse passiveFault indication Output testing Current sourcePower supply options 85 to 250 VAC Local display optionalEnvironmental limits Temperature Operating Process fluid vs. ambient temperature20 to 30 VDC StorageVibration limits Humidity limitsDensity limits Ambient temperature effect on milliamp output Shipping weightEnvironmental effects Hazardous area classificationsPage Appendix B Hart Communicator Menu TreesHart Communicator Menu Trees Installing the Optional Display Appendix CInstalling the Optional Display New and unused equipment Return PolicyUsed equipment Page Index AtexHart Customer service Index Page 3100572