Emerson IFT9701 instruction manual Conditions indicated by optional LCD, Power supply

Page 67

Troubleshooting continued

Table 8-2 Conditions indicated by optional LCD

Optional LCD reads:

Condition

 

 

Mass or volume flow rate (such as “100.00”)

Normal operation

 

 

“OL0”

Flow rate has exceeded upper limit of display

 

 

“ 88.8.8.0”

Startup and initialization

 

 

“ZERO0”

Zero in progress

 

 

“SLUG0”

Slug flow (density below or above user-defined limits)

 

 

“ELEC0”

Transmitter hardware failure, zero failure

 

 

“SENS0”

Sensor failure, faulty cable, process over range, density above or

 

below transmitter limits

 

 

Remains OFF

Power supply failure

 

 

8.4Power supply

If power supply wiring is installed incorrectly, or the flowmeter is improperly grounded, the meter will not operate properly. Follow these steps to check power supply wiring and grounding:

1.If a switch was installed in the power supply line, be sure the switch is in the ON position.

2.Check the power supply voltage, and make sure it matches the voltage listed on the label in the flowmeter’s power supply wiring compartment. See Figure 8-2.

3.Turn power supply OFF.

WARNING

Line voltage can cause electric shock or flowmeter damage.

Disconnect power before accessing power supply terminals.

4.At the terminals indicated in Figure 8-2, make sure wires are secured tightly and making good connections. Make sure no bare wires remain exposed.

5.Wiring must be 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire.

6.Maximum wire lengths for a DC power supply are as follows:

Power-supply wire size

Maximum length

 

 

 

16

AWG (1,5 mm²)

1500 feet (450 meters)

 

 

 

18

AWG (0,75 mm²)

1000 feet (300 meters)

 

 

 

20

AWG (0,5 mm²)

600 feet (200 meters)

 

 

 

Flowmeter Startup

Configuration with Communicator

Configuration with ProLink II

Troubleshooting

Model IFT9701 Transmitter Instruction Manual

59

Image 67
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page Before You Begin About this manual SafetyDefinitions European installationsFlowmeter components Remotely mounted IFT9701 transmitter Page Getting Started Safety, reliability, accessibilityHazardous area Orientation and mounting Temperature, humidity, and vibrationTransmitters approved for Atex Zone Visibility of tagsCompartment tags and lockout device Jumper settingsSecurity Fault output levelsRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Cable types Connecting the transmitter to the sensorCable selection guidelines Temperature ranges for jacket materialGuidelines for conduit Wiring connections to sensorGuidelines for cable gland Sensor terminal designations Cable connections to sensorsSensor wiring compartment and sensor wiring terminals Wiring guidelines Power Supply and Output WiringPower supply wiring terminals Connect power supply wiringConnect output wiring Wire guidelines for DC power supplyMilliamp output performance Milliamp outputMilliamp output connected to Bell 202 multidrop network Typical Hart network wiringHart Communicator connections Communication tools connected to milliamp outputPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Zeroing Customer serviceStartup procedures Flowmeter StartupInitialization Diagnostic LEDStartup mode Operating modeFlowmeter zeroing Zeroing procedureDiagnosing zero failure Configuration, calibration, and characterizationProcess measurement Page Configuration overview Configuration with a Hart CommunicatorHart tag Configuration parametersMeasurement units Mass flow unit Software label Volume flow unit Measurement units for mass and volume flowDamping Flow cutoffEffect of flow direction on outputs and totalizers Flow directionPulse output scaling Range values for milliamp outputAuto zero Calibration proceduresDiagnosing zeroing failure Flow calibration procedureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Process variable measurement Configuration window Flow panelMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Configuration window Analog Output panel Output configurationConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel Transmitter diagnostic tools TroubleshootingGeneral guidelines Optional LCD Fault outputsNormal conditions indicated by LED Conditions indicated by optional LCD Power supplyWiring Power supply connectionsOver range and sensor failure conditions Normal resistance and voltage ranges for flowmeter circuitsSlug flow Troubleshooting over range and sensor failure conditionsTransmitter failure Digital diagnostic messagesPage Pulse passive IFT9701 SpecificationsPerformance specifications Functional specifications Output signals Milliamp activeLocal display optional Fault indicationOutput testing Current source Power supply options 85 to 250 VACStorage Environmental limits Temperature OperatingProcess fluid vs. ambient temperature 20 to 30 VDCVibration limits Humidity limitsDensity limits Hazardous area classifications Ambient temperature effect on milliamp outputShipping weight Environmental effectsPage Hart Communicator Menu Trees Appendix BHart Communicator Menu Trees Appendix C Installing the Optional DisplayInstalling the Optional Display New and unused equipment Return PolicyUsed equipment Page Atex IndexHart Customer service Index Page 3100572