Page 62

Configuration with ProLink II Software continued

Use a mass flow unit during the calibration procedure. If the application requires volume flow measurement, choose a mass flow unit for the flow calibration, then choose a volume flow unit for the application.

To calculate the flow calibration factor:

1.Configure the transmitter to use a mass flow measurement unit (see Section 7.2.2).

2.In the Flow panel (depicted in Figure 7-2), enter the flowmeter’s 8-digit flow calibration factor into the Flow Cal text box. The flow calibration factor can be found on the flowmeter’s serial number tag, or on the certificate that is shipped with the sensor.

3.Zero the flowmeter (see Section 7.3.1).

4.With flow through the meter completely stopped, from the ProLink menu, click on Totalizer Control. The Totalizer Control window is displayed, as depicted in Figure 7-6.

Figure 7-6 Totalizer Control window

5. Click the Reset button to reset the internal totalizer to zero.

54

Model IFT9701 Transmitter Instruction Manual

Image 62
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page About this manual Safety Before You BeginFlowmeter components European installationsDefinitions Remotely mounted IFT9701 transmitter Page Hazardous area Safety, reliability, accessibilityGetting Started Temperature, humidity, and vibration Orientation and mountingVisibility of tags Transmitters approved for Atex ZoneJumper settings Compartment tags and lockout deviceFault output levels SecurityRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Connecting the transmitter to the sensor Cable typesTemperature ranges for jacket material Cable selection guidelinesGuidelines for cable gland Wiring connections to sensorGuidelines for conduit Cable connections to sensors Sensor terminal designationsSensor wiring compartment and sensor wiring terminals Power Supply and Output Wiring Wiring guidelinesConnect power supply wiring Power supply wiring terminalsWire guidelines for DC power supply Connect output wiringMilliamp output Milliamp output performanceTypical Hart network wiring Milliamp output connected to Bell 202 multidrop networkCommunication tools connected to milliamp output Hart Communicator connectionsPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Flowmeter Startup Customer serviceStartup procedures ZeroingOperating mode Diagnostic LEDStartup mode InitializationZeroing procedure Flowmeter zeroingConfiguration, calibration, and characterization Diagnosing zero failureProcess measurement Page Configuration with a Hart Communicator Configuration overviewMeasurement units Configuration parametersHart tag Measurement units for mass and volume flow Mass flow unit Software label Volume flow unitFlow cutoff DampingFlow direction Effect of flow direction on outputs and totalizersRange values for milliamp output Pulse output scalingCalibration procedures Auto zeroFlow calibration procedure Diagnosing zeroing failureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Configuration window Flow panel Process variable measurementMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Output configuration Configuration window Analog Output panelConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel General guidelines TroubleshootingTransmitter diagnostic tools Normal conditions indicated by LED Fault outputsOptional LCD Power supply Conditions indicated by optional LCDPower supply connections WiringNormal resistance and voltage ranges for flowmeter circuits Over range and sensor failure conditionsTroubleshooting over range and sensor failure conditions Slug flowDigital diagnostic messages Transmitter failurePage Functional specifications Output signals Milliamp active IFT9701 SpecificationsPerformance specifications Pulse passivePower supply options 85 to 250 VAC Fault indicationOutput testing Current source Local display optional20 to 30 VDC Environmental limits Temperature OperatingProcess fluid vs. ambient temperature StorageDensity limits Humidity limitsVibration limits Environmental effects Ambient temperature effect on milliamp outputShipping weight Hazardous area classificationsPage Appendix B Hart Communicator Menu TreesHart Communicator Menu Trees Installing the Optional Display Appendix CInstalling the Optional Display Used equipment Return PolicyNew and unused equipment Page Index AtexHart Customer service Index Page 3100572