Emerson IFT9701 instruction manual Wire guidelines for DC power supply, Connect output wiring

Page 29

Power Supply and Output Wiring continued

Table 4-1 Wire guidelines for DC power supply

Wire size

Wire length

 

 

 

16

AWG (1,5 mm²)

1500 feet (450 meters)

 

 

 

18

AWG (0,75 mm²)

1000 feet (300 meters)

 

 

 

20

AWG (0,5 mm²)

600 feet (200 meters)

 

 

 

4.4Connect output wiring

Figure 4-2 shows the milliamp and pulse output terminals.

Install twisted-pair, shielded cable, consisting of 20 AWG (0,5 mm²) to 16 AWG (1,5 mm²) wire.

For basic information on milliamp output wiring, see Section 4.4.1.

For instructions on connecting the milliamp output to a Bell 202 multidrop network, see Section 4.4.2.

For instructions on connecting a HART device to the milliamp output, see Section 4.4.3.

For instructions on pulse output wiring, see Section 4.4.4.

Figure 4-2 Output wiring terminals

Active milliamp output

Passive pulse output

Internally powered

Requires pull-up resistor

 

to external 5–30 VDC

 

power supply

Conduit opening for output wiring

Field wiring compartment

 

Sensor wiring

Case ground

compartment

Terminate output cable shielding at gland or conduit fitting.

360° termination of shielding is not necessary.

Do not terminate shield inside wiring compartment.

The pull-up resistor must be of sufficient value to limit the total loop current to less than 500 ohms. Refer to Section 4.4.4 to determine the pull-up resistor needed.

Before You Begin

Getting Started

Mounting the Remote Transmitter

Power Supply and Output Wiring

Model IFT9701 Transmitter Instruction Manual

21

Image 29
Contents Micro Motion Page Micro Motion Page Contents Flowmeter Startup Index Page Before You Begin About this manual SafetyFlowmeter components European installationsDefinitions Remotely mounted IFT9701 transmitter Page Hazardous area Safety, reliability, accessibilityGetting Started Orientation and mounting Temperature, humidity, and vibrationTransmitters approved for Atex Zone Visibility of tagsCompartment tags and lockout device Jumper settingsSecurity Fault output levelsRe-installing the circuit board compartment cover Remotely Mounting the Transmitter Installation dimensions for remote mounting Mounting the transmitter to a wall or other surface Cable types Connecting the transmitter to the sensorCable selection guidelines Temperature ranges for jacket materialGuidelines for cable gland Wiring connections to sensorGuidelines for conduit Sensor terminal designations Cable connections to sensorsSensor wiring compartment and sensor wiring terminals Wiring guidelines Power Supply and Output WiringPower supply wiring terminals Connect power supply wiringConnect output wiring Wire guidelines for DC power supplyMilliamp output performance Milliamp outputMilliamp output connected to Bell 202 multidrop network Typical Hart network wiringHart Communicator connections Communication tools connected to milliamp outputPulse output Wiring to pulse counter with internal pull-up resistor Wiring to Series 3000 applications platform with I/O cable Page Startup procedures Customer serviceFlowmeter Startup ZeroingStartup mode Diagnostic LEDOperating mode InitializationFlowmeter zeroing Zeroing procedureDiagnosing zero failure Configuration, calibration, and characterizationProcess measurement Page Configuration overview Configuration with a Hart CommunicatorMeasurement units Configuration parametersHart tag Mass flow unit Software label Volume flow unit Measurement units for mass and volume flowDamping Flow cutoffEffect of flow direction on outputs and totalizers Flow directionPulse output scaling Range values for milliamp outputAuto zero Calibration proceduresDiagnosing zeroing failure Flow calibration procedureTotal Characterization Configuration with ProLink II Software Configuration window Device panel Process variable measurement Configuration window Flow panelMass flow unit Software label Volume flow unit Effect of flow direction on outputs and totalizers Configuration window Analog Output panel Output configurationConfiguration window Frequency panel Configuration with ProLink II Software Flow Calibration dialog box Diagnosing zeroing failure Totalizer Control window Characterization Configuration window Density panel General guidelines TroubleshootingTransmitter diagnostic tools Normal conditions indicated by LED Fault outputsOptional LCD Conditions indicated by optional LCD Power supplyWiring Power supply connectionsOver range and sensor failure conditions Normal resistance and voltage ranges for flowmeter circuitsSlug flow Troubleshooting over range and sensor failure conditionsTransmitter failure Digital diagnostic messagesPage Performance specifications IFT9701 SpecificationsFunctional specifications Output signals Milliamp active Pulse passiveOutput testing Current source Fault indicationPower supply options 85 to 250 VAC Local display optionalProcess fluid vs. ambient temperature Environmental limits Temperature Operating20 to 30 VDC StorageDensity limits Humidity limitsVibration limits Shipping weight Ambient temperature effect on milliamp outputEnvironmental effects Hazardous area classificationsPage Hart Communicator Menu Trees Appendix BHart Communicator Menu Trees Appendix C Installing the Optional DisplayInstalling the Optional Display Used equipment Return PolicyNew and unused equipment Page Atex IndexHart Customer service Index Page 3100572