Hoshizaki KM-650MWH, KM-650MAH, KM-650MRH service manual Harvest Timer dip switch 1

Page 20

c)Harvest Timer (dip switch 1 & 2)

The harvest timer starts counting when the thermistor reads 48°F (9°C) at the evaporator outlet.

No adjustment is required under normal use, as the harvest timer is adjusted to the suitable position. However, a setting longer than the factory setting may be advised in cases where the flush provided at harvest needs to be prolonged for extra cleaning. Before changing this setting, call the HOSHIZAKI Technical Support Department at

18002331940 for recommendations. Keep in mind that setting the harvest timer to a longer setting will decrease 24 hour production.

Dip Switch Setting

Time

No. 1

No. 2

(seconds)

 

OFF

OFF

60

ON

OFF

90

OFF

ON

120

ON

ON

180

d)Pump-Out Timer (dip switch 3 & 4)

When a freeze cycle is completed, the pump motor stops, and the icemaker resumes operation in 2 seconds. Then, during cycles when a pump out is called for, the pump motor drains the water tank for the time determined by the pump-out timer. The pump- out timer also acts in place of the harvest timer during cycles with a pump out.

The pump-out timer is factory-adjusted, and no adjustment is required.

Dip Switch Setting

Time (seconds)

No. 3

No. 4

T1

T2

OFF

OFF

10

150

ON

OFF

10

180

OFF

ON

10

120

ON

ON

20

180

T1: Time to drain the water tank

T2: Harvest timer at pump out

Pump out always occurs on the 2nd harvest after startup. Then, depending on the pump- out frequency control setting (dip switch 5 & 6), pump out occurs every cycle, or every 2nd, 5th or 10th cycle.

20

Image 20
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page Specifications Icemaker KM-650MAH air-cooledKM-650MWH water-cooled Water Cooled CondenserKM-650MRH remote air-cooled Condensing Unit URC-5FSpecifications Model URC-5FII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Board Control Products E Control BoardControl Board Layout Features Maximum Water Supply Period 6 minutesLED Lights and Audible Alarm Safeties Controls and Adjustments Default Dip Switch SettingsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Check Procedure Control Board ReplacementKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled Wiring Diagrams KM-650MAH air-cooled and KM-650MWH water-cooledPsig Performance Data 108680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure Diagnostic Charts No Ice ProductionProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Other Low Ice ProductionAbnormal Ice Problem Possible Cause Remedy Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Evacuation and Recharge R-404ARemoval and Replacement of Compressor BrazingRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Thermistor Removal and Replacement of Fan MotorRemoval and Replacement of Inlet Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Cleaning and Sanitizing ProceduresCleaning Procedure Stainless Steel Exterior MaintenanceSanitizing Procedure Following Cleaning Procedure Preparing the Icemaker for Long Storage Storage Bin and ScoopAir Filters air-cooled models only Condenser air-cooled and remote air-cooled models onlyDrain the potable water supply line Drain the potable water tank