Hoshizaki KM-650MAH, KM-650MRH Adjustment of Water Regulating Valve Water-Cooled Model Only

Page 45

7)Remove the screws and the valve from the bracket.

8)Install the new valve.

9)Remove the drier, then place the new drier in position.

10)Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.

11)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

12)Evacuate the system, and charge it with refrigerant. See the nameplate for the required refrigerant charge.

13)Connect the flare-connections.

14)Open the water supply line shut-off valve.

15)Check for water leaks.

16)Replace the panels in their correct positions.

17)Turn on the power supply.

I.Adjustment of Water Regulating Valve - Water-Cooled Model Only

The water regulating valve (also called "water regulator") is factory-adjusted. No adjustment is required under normal use. Adjust the water regulator, if necessary, using the following procedures.

1)Prepare a thermometer to check the condenser drain temperature. Attach a pressure gauge to the high-side line of the system.

2)Five minutes after a freeze cycle starts, confirm that the thermometer reads 104°F to 115°F (40°C to 46°C). If it does not, rotate the adjustment screw by using a flat blade screwdriver until the temperature is in the proper range. See Fig. 1. Next, check that the reference pressure is in the range indicated in the Head Pressure table in the Performance Data section. If it is not in the proper range, verify the refrigerant charge.

3)Check that the condenser drain temperature is stable.

Adjustment

Screw

CW – Higher

CCW – Lower

Top View

Fig. 1

45

Image 45
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page KM-650MAH air-cooled Specifications IcemakerWater Cooled Condenser KM-650MWH water-cooledKM-650MRH remote air-cooled URC-5F Condensing UnitModel URC-5F SpecificationsII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Products E Control Board Control Board LayoutControl Board Maximum Water Supply Period 6 minutes FeaturesLED Lights and Audible Alarm Safeties Default Dip Switch Settings Controls and AdjustmentsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Replacement Control Board Check ProcedureKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled KM-650MAH air-cooled and KM-650MWH water-cooled Wiring DiagramsPsig 108 Performance Data680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure No Ice Production Diagnostic ChartsProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Low Ice Production Abnormal IceOther Problem Possible Cause Remedy Service for Refrigerant Lines Removal and Replacement of ComponentsRefrigerant Recovery Evacuation and Recharge R-404ABrazing Removal and Replacement of CompressorRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Fan Motor Removal and Replacement of ThermistorRemoval and Replacement of Pump Motor Removal and Replacement of Inlet Water ValveRemoval and Replacement of Spray Tubes Cleaning and Sanitizing Procedures VI. Cleaning and Maintenance InstructionsCleaning Procedure Maintenance Sanitizing Procedure Following Cleaning ProcedureStainless Steel Exterior Storage Bin and Scoop Preparing the Icemaker for Long StorageAir Filters air-cooled models only Condenser air-cooled and remote air-cooled models onlyDrain the potable water tank Drain the potable water supply line