Hoshizaki KM-650MAH, KM-650MRH, KM-650MWH service manual Pump-Out Frequency Control dip switch 5

Page 21

e)Pump-Out Frequency Control (dip switch 5 & 6)

The pump motor drains the water tank at the frequency set by the pump-out frequency control.

The pump-out frequency control is factory-adjusted to drain the water tank every 10 cycles, and no adjustment is required. However, where water quality is bad and the icemaker needs a pump drain more often, the pump-out frequency can be adjusted as shown in the table below.

Dip Switch Setting

Frequency

No. 5

No. 6

 

OFF

OFF

every cycle

ON

OFF

every 2 cycles

OFF

ON

every 5 cycles

ON

ON

every 10 cycles

f) Freeze Timer (dip switch 9 & 10)

CAUTION

Adjust to proper specification, or the unit may not operate correctly.

The freeze timer setting determines the maximum allowed freeze time to prevent possible freeze-up issues. Upon termination of freeze timer, machine initiates the harvest cycle. After 2 consecutive timer terminations, machine will shut down, possibly indicating a problem.

The freeze timer is factory adjusted and no adjustment is required.

Dip Switch Setting

Time

No. 9

No. 10

(minutes)

 

OFF

OFF

60

 

 

 

OFF

ON

50

ON

OFF

70

ON

ON

60

g) Bin Control

CAUTION

When the ambient temperature is below 45°F (7°C), the bin control thermostat operates to stop the icemaker even if the ice storage bin is empty. When the thermostat is set in the prohibited range, the icemaker operates continuously even if the ice storage bin is filled with ice. Setting in the prohibited range might cause severe damage to the icemaker resulting in failure.

No adjustment is required under normal use, as the bin control is factory-adjusted. Adjust it, if necessary, so that the icemaker stops automatically within 10 seconds after ice contacts the bin control thermostat bulb.

21

Image 21
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page KM-650MAH air-cooled Specifications IcemakerWater Cooled Condenser KM-650MWH water-cooledKM-650MRH remote air-cooled URC-5F Condensing UnitModel URC-5F SpecificationsII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Products E Control Board Control Board LayoutControl Board Maximum Water Supply Period 6 minutes FeaturesLED Lights and Audible Alarm Safeties Default Dip Switch Settings Controls and AdjustmentsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Replacement Control Board Check ProcedureKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled KM-650MAH air-cooled and KM-650MWH water-cooled Wiring DiagramsPsig 108 Performance Data680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure No Ice Production Diagnostic ChartsProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Low Ice Production Abnormal IceOther Problem Possible Cause Remedy Service for Refrigerant Lines Removal and Replacement of ComponentsRefrigerant Recovery Evacuation and Recharge R-404ABrazing Removal and Replacement of CompressorRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Fan Motor Removal and Replacement of ThermistorRemoval and Replacement of Pump Motor Removal and Replacement of Inlet Water ValveRemoval and Replacement of Spray Tubes Cleaning and Sanitizing Procedures VI. Cleaning and Maintenance InstructionsCleaning Procedure Maintenance Sanitizing Procedure Following Cleaning ProcedureStainless Steel Exterior Storage Bin and Scoop Preparing the Icemaker for Long StorageAir Filters air-cooled models only Condenser air-cooled and remote air-cooled models onlyDrain the potable water tank Drain the potable water supply line