Hoshizaki KM-650MRH, KM-650MAH, KM-650MWH Control Board Check Procedure, Control Board Replacement

Page 22

4. Control Board Check Procedure

Before replacing a control board that does not show a visible defect and that you suspect is bad, always conduct the following check procedure. This procedure will help you verify your diagnosis.

1)Check the dip switch settings to assure that #3, 4, 7, 8, 9, & 10 are in the factory default position. On units with a slide-type output test switch, the output test switch (S3) should be OFF. Switches 1, 2, 5, & 6 are cleaning adjustments and the settings are flexible.

2)Turn the control switch to ICE and check for proper control voltage. If the red LED is ON, the control voltage is good. If the red LED is OFF, check the control transformer circuit.

3)Check the 115 volt input at the 10-pin connector. Check the brown wire at pin #10 to a white neutral wire for 115 volts. (Always choose a white neutral wire to establish a good neutral connection when checking voltages.) A jumper also feeds 115 volts into pin #7. If no voltage is present, check the 115 volt supply circuit.

4)The output test switch provides a relay sequence test. On units with a slide-type output test switch, move the control switch to the OFF position, move the output test switch to the ON position, then move the control switch to the ICE position. On units with a push- type output test switch, make sure the control switch is in the ICE position, then press the output test switch. The correct lighting sequence should be none, 2, 3, 4, 1, and 4, normal sequence every 5 seconds. Components (e.g., the compressor) will cycle during the test. Note that the order of the relays from the outer edge of the board is 1, 4, 3, 2. Note: If the LEDs light in a different sequence or the 5–second interval does not occur,

the control board is bad and should be replaced.

5)After checking the sequence, place the output test switch back in the OFF position

on units with a slide-type switch. The output test switch must remain in the OFF position during normal operation. On units with a push-type output test switch, the unit automatically resumes normal operation after the test. The unit begins normal operation with the 1 minute fill cycle.

5. Control Board Replacement

The application switch located between relay X3 & X4 must be set to match the original board application. Place this switch in the ALP position if there is no white wire supplied to the K1 connector. If there is a white wire, place the switch in the C position. If this switch is placed in the wrong position either the compressor contactor will remain energized with the control switch OFF or the unit will not start.

The dip switches should be adjusted to the factory default settings as outlined in this manual. Dip switch #8 must remain in the OFF position.

22

Image 22
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page Specifications Icemaker KM-650MAH air-cooledKM-650MWH water-cooled Water Cooled CondenserKM-650MRH remote air-cooled Condensing Unit URC-5FSpecifications Model URC-5FII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Board Layout Control Products E Control BoardControl Board Features Maximum Water Supply Period 6 minutesLED Lights and Audible Alarm Safeties Controls and Adjustments Default Dip Switch SettingsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Check Procedure Control Board ReplacementKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled Wiring Diagrams KM-650MAH air-cooled and KM-650MWH water-cooledPsig Performance Data 108680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure Diagnostic Charts No Ice ProductionProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Abnormal Ice Low Ice ProductionOther Problem Possible Cause Remedy Refrigerant Recovery Removal and Replacement of ComponentsService for Refrigerant Lines Evacuation and Recharge R-404ARemoval and Replacement of Compressor BrazingRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Thermistor Removal and Replacement of Fan MotorRemoval and Replacement of Inlet Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Cleaning and Sanitizing ProceduresCleaning Procedure Sanitizing Procedure Following Cleaning Procedure MaintenanceStainless Steel Exterior Air Filters air-cooled models only Preparing the Icemaker for Long StorageStorage Bin and Scoop Condenser air-cooled and remote air-cooled models onlyDrain the potable water supply line Drain the potable water tank
Related manuals
Manual 32 pages 59.37 Kb