6)A liquid charge is recommended for charging an R-404A system. Invert the service cylinder and place it on scales. Open the high-side, service manifold valve.

7)Allow the system to charge with liquid until the proper charge weight is met.

8)If necessary, add any remaining charge to the system through the low-side. Use a throttling valve or liquid dispensing device to add the remaining liquid charge through the low-side access port with the unit running.

9)Close the two refrigerant access valves, and disconnect the service manifold hoses.

10)Cap the access valves to prevent a possible leak.

B.Brazing

DANGER

1.Refrigerant R-404A itself is not flammable at atmospheric pressure and temperatures up to 176°F (80°C).

2.Refrigerant R-404A itself is not explosive or poisonous. However, when exposed to high temperatures (open flames) R-404A can be decomposed to form hydrofluoric acid and carbonyl fluoride both of which are hazardous.

3.Always recover the refrigerant and store it in an approved container. Do not discharge the refrigerant into the atmosphere.

4.Do not use silver alloy or copper alloy containing arsenic.

5.Do not use R-404A as a mixture with pressurized air for leak testing. Refrigerant leaks can be detected by charging the unit with a little refrigerant, raising the pressure with nitrogen and using an electronic leak detector.

Note: Because the pipes in the evaporator case are specially coated to resist corrosion, it is important to make connections outside the evaporator case when possible. If it is necessary to braxe inside the evaporator case, use sandpaper to remove the coating from the brazing connections before unbrazing the components.

C. Removal and Replacement of Compressor

IMPORTANT

Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.

Note: When replacing a compressor with a defective winding, be sure to install the new start capacitor and start relay supplied with the replacement compressor. Due to the ability of the POE oil in the compressor to absorb moisture quickly, the compressor must not be opened more than 15 minutes for replacement or service. Do not mix lubricants of different compressors even if both are charged with R-404A, except when they use the same lubricant.

1) Turn off the power supply.

40

Image 40
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page Specifications Icemaker KM-650MAH air-cooledKM-650MWH water-cooled Water Cooled CondenserKM-650MRH remote air-cooled Condensing Unit URC-5FSpecifications Model URC-5FII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Board Layout Control Products E Control BoardControl Board Features Maximum Water Supply Period 6 minutesLED Lights and Audible Alarm Safeties Controls and Adjustments Default Dip Switch SettingsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Check Procedure Control Board ReplacementKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled Wiring Diagrams KM-650MAH air-cooled and KM-650MWH water-cooledPsig Performance Data 108680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure Diagnostic Charts No Ice ProductionProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Abnormal Ice Low Ice Production Other Problem Possible Cause Remedy Removal and Replacement of Components Service for Refrigerant LinesRefrigerant Recovery Evacuation and Recharge R-404ARemoval and Replacement of Compressor BrazingRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Thermistor Removal and Replacement of Fan MotorRemoval and Replacement of Inlet Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Cleaning and Sanitizing ProceduresCleaning Procedure Sanitizing Procedure Following Cleaning Procedure MaintenanceStainless Steel Exterior Preparing the Icemaker for Long Storage Storage Bin and ScoopAir Filters air-cooled models only Condenser air-cooled and remote air-cooled models onlyDrain the potable water supply line Drain the potable water tank