J. Removal and Replacement of Headmaster (Condensing Pressure

Regulator - C.P.R.) - Remote Air-Cooled Model Only

IMPORTANT

Always install a new drier every time the sealed refrigeration system is opened. Do not replace the drier until after all other repair or replacement has been made.

1)Turn off the power supply.

2)Remove the panels from the remote condenser unit.

3)Recover the refrigerant and store it in an approved container.

4)Before heating, break off the stub on the dome to release the dome charge.

5)Disconnect the headmaster.

6)Place the new headmaster in position.

7)Remove the drier, then place the new drier in position.

8)Braze all fittings with nitrogen gas flowing at a pressure of 3 to 4 PSIG.

CAUTION

Always protect the headmaster body by using a damp cloth to prevent it from overheating. Do not braze with the headmaster body exceeding 250°F (121°C).

9)Check for leaks using nitrogen gas (140 PSIG) and soap bubbles.

10)Evacuate the system and charge it with refrigerant. See the charge label in the machine compartment for the required refrigerant charge.

11)Replace the panels in their correct positions.

12)Turn on the power supply.

46

Image 46
Contents KM-650MAH KM-650MWH KM-650MRH Hoshizaki AMERICA, INC Contents Page Specifications Icemaker KM-650MAH air-cooledKM-650MWH water-cooled Water Cooled CondenserKM-650MRH remote air-cooled Condensing Unit URC-5FSpecifications Model URC-5FII. General Information Construction KM-650MWH water-cooled KM-650MRH remote air-cooled Sequence of Operation Cycle Steps Harvest Cycle Freeze Cycle One Minute Control Board Control Board Layout Control Products E Control BoardControl Board Features Maximum Water Supply Period 6 minutesLED Lights and Audible Alarm Safeties Controls and Adjustments Default Dip Switch SettingsHarvest Timer dip switch 1 Pump-Out Frequency Control dip switch 5 Control Board Check Procedure Control Board ReplacementKM-650MAH air-cooled KM-650MWH water-cooled KM-650MRH remote air-cooled Wiring Diagrams KM-650MAH air-cooled and KM-650MWH water-cooledPsig Performance Data 108680 615 IV. Service Diagnosis Minute KM Diagnostic Procedure Diagnostic Charts No Ice ProductionProblem Possible Cause Remedy Problem Possible Cause Remedy Problem Possible Cause Remedy Evaporator is Frozen Up Abnormal Ice Low Ice ProductionOther Problem Possible Cause Remedy Refrigerant Recovery Removal and Replacement of ComponentsService for Refrigerant Lines Evacuation and Recharge R-404ARemoval and Replacement of Compressor BrazingRemoval and Replacement of Drier Removal and Replacement of Expansion Valve Removal and Replacement of Hot Gas Valve and Line Valve Removal and Replacement of Evaporator Adjustment of Water Regulating Valve Water-Cooled Model Only Page Removal and Replacement of Thermistor Removal and Replacement of Fan MotorRemoval and Replacement of Inlet Water Valve Removal and Replacement of Pump MotorRemoval and Replacement of Spray Tubes VI. Cleaning and Maintenance Instructions Cleaning and Sanitizing ProceduresCleaning Procedure Sanitizing Procedure Following Cleaning Procedure MaintenanceStainless Steel Exterior Air Filters air-cooled models only Preparing the Icemaker for Long StorageStorage Bin and Scoop Condenser air-cooled and remote air-cooled models onlyDrain the potable water supply line Drain the potable water tank