Electrical Sequence

Electrical Sequence:

There are 7 indicator lights on the control board:

●WTR-OK:(Water OK) Green. Normal=Glowing. Glow when there is water in the reservoir.

●PWR-OK:(Power OK) Green. Normal=Glowing. Glows when the power board has power and is functional.

●Service: Red. Normally Off.

●Freeze: Red. Normally glowing when making ice.

●Bin Full: Red. Normally Off when making ice.

●LED1: White. Located next to the Control Board’s Compressor Relay. Normally glowing when making ice.

●LED2: White. Located next to the Control Board’s Auger Motor Relay. Normally glowing when making ice.

If the machine is switched OFF at the mode switch, but otherwise ready to go, switching the mode switch ON does the following:

●The PWR-OKlight glows.

●If there is water in the float reservoir, the WTR-OKlight glows.

●After 10 seconds the Freeze, LED1 and LED3 lights glow and the machine starts up.

Start Up:

●The compressor relay and auger motor relay become energized, connecting power to the windings of the auger motor and contactor coil.

●The contactor is energized, connecting power to the compressor, and the compressor starts.

●As ice is made it passes between the ice level sensors but because it is not a continuous stream it only interrupts the sensor’s infrared beam momentarily. The bin full light remains off and the machine stays on until ice builds up in the bin and blocks the path between the sensors for 6 seconds or longer. When that occurs the bin full light glows and the machine shuts down.

Shut Down:

●The compressor relays opens, LED1 goes out. ●The compressor contactor opens.

●The auger motor stays on for 1 more minute, clearing out ice in the evaporator, and then ●The auger motor relay opens, LED3 goes out and the auger motor stops.

The compressor will not restart until 2 minutes or more have passed after last shutdown. If the path between the ice level sensors remains clear for more than 10 seconds the ice machine will restart.

Control Board Protection Devices:

●When the water level in the reservoir falls below the water level sensor’s tip, the WTR-OKlight goes out and the machine shuts down. When water refills the reservoir the WTR-OKlight glows and the machine starts up again.

●If the auger drive motor currents becomes excessive the compressor and auger drive motor will be switched OFF and the Service light will blink. The control board will restart the auger drive motor in 4 minutes. If during the first 60 seconds after restart the auger motor current stays within limits, the compressor is restarted and the machine returns to normal operation. If the auger motor’s current is excessive within 60 seconds after restart, the process will be repeated once more. If during that try the current is still excessive the machine shuts down and must be manually reset. The Service light will then be glowing continuously.

To Reset:

●Switch power to the unit off and then back on.

Other Protection Devices:

●If the high pressure control cut out switch opens the machine will stop immediately. It will automatically reset when the high pressure falls below its cut in point.

●If the low pressure control cut out switch opens the machine will stop immediately. It will automatically reset when the pressure rises above its cut in point.

●The mode (ON-OFF)switch is the manual control for the complete machine, but it is not a service disconnect.

Page 19

Image 25
Contents By Ice-O-Matic Pearl Ice SeriesPage Keep this manual for future reference IntroductionTable Of Contents Inspect Promptly Freight Claim ProcedureVisible Loss or Damage Concealed Loss or DamageGoverning LAW WarrantyFor the Installer GEM0650/0956R GEM1256R Bin Application Ice Machine SpecificationsStorage Bin LocationIce machine Water LimitationsRemote Condenser ERC Dimensions Inches GRC1001 GRC1061 GCR2061Pearl Ice Number Line SetsCalculation Formula Remote Condenser LocationCalculation Example Roof Attachment Remote Condenser LocationPrecharged Line Set Routing Typical Installation Final Connections Coupling Instructions Initial ConnectionsWater Inlet For the PlumberDrains Ice Machine For the Electrician Completed Installation Final Check List Start Up There are no adjustments to make, so replace the panelsPre-Start Inspection Start UpComponent Description Control Board GEM0650/0956/1256 Remote Electrical Sequence Water Operation WaterWater Level Water SystemOperation Refrigeration Refrigeration SchematicLow Condensing Temperature Pump Down Operation Performance Sanitizing and Cleaning Brush in direction of fins Condenser MaintenanceBearing Maintenance Bearing MaintenanceBin Control Sensor Sensor MaintenanceWater Sensor Auger Auger MaintenanceSymptom Possible Cause Probable Correction Service DiagnosisSymptom High pressure cut out check Control System DiagnosticsWater Reservoir Water Reservoir, Bin ControlBin Controls Ice Level Sensors Bearing and Breaker To Remove the Breaker Bearing AssemblyTo Remove the Auger AugerTo Remove the Water Seal Water SealRemoval of the Water Seal To Replace the Water Seal Replacing the Water SealTo Replace the Evaporator EvaporatorTo Reassemble the Evaporator and Auger Gear Motor To Remove and Repair the Gear Motor AssemblyTo Check the Gear Motor To Inspect the Gear MotorFan Blade and Motor To Remove the Condenser Fan Motor AssemblyCharging Procedure Refrigeration ServiceWiring Diagram GEM0650R GEM0650R Wiring DiagramWiring Diagram GEM0956R GEM0956R Wiring DiagramWiring Diagram GEM1256R GEM1256R Wiring DiagramWhat to Do Before Calling for Service Service History