GEM0650/0956/1256 Remote | For the Installer |
Final Check List
___1. Is the ice system installed indoors in a location where air and water temperatures are controlled, and where they do not exceed the design limitations?
___2. Is there an electrical service within sight of the installed machine? Has the voltage been checked, and compared to nameplate requirements?
___3. Have all the plumbing connections been made and checked for leaks?
___4. Has the machine and bin been leveled?
___5. Is there a minimum of 6 inches clearance at the rear, left and right of the machine for proper service access?
___6. Is the water pressure a minimum of 20 psig?
___7. Has the machine been secured to the bin or dispenser?
___8. Is there a water shut off valve installed near the machine?
___9. Is the remote condenser installed per local codes, and in a place where it has adequate ventilation and minimal solar heat gain?
___10. Has all shipping material and literature (inside front panel) been removed from the units?
___11.Have the remote condenser and
Condenser Leveled?
Roof Holes Sealed?
Remote condenser |
| Machine Leveled? |
secured? |
|
|
|
|
|
Plumbing?
Power Supply?
___12. Has the electrical connection between the ice maker and condenser been made?
___13. Verify that the master switch is in the OFF position.
___14. Switch ON the electrical power.
___15. Refer to the