Vulcan-Hart ML-136647, ML-136654 GAS Connection, GAS Pressures ALL Models, Fryers with Casters

Page 8

GBD_GBDF SERIES GAS FRYERS

GAS CONNECTION

All gas supply connections and any pipe joint compound must be resistant to the action of propane gases.

The gas inlet is located on the lower rear of the fryer. Codes require that a gas shutoff valve be installed in the gas line ahead of the fryer.

The gas supply line must be at least the equivalent of ½” (12.7 mm) iron pipe for single units and 1-1/4” (31.75 mm) for batteries. If using the optional quick-disconnect flex hose, ¾” (19 mm) iron pipe for single units and 1-1/4” (31.75 cm) iron pipe for batteries.

Make sure the pipes are clean and free of obstructions, dirt, and piping compound. A battery requires one or two connections of appropriate size for the gas requirement.

Prior to lighting, check all joints in the gas supply line for leaks. Use soap and water solution. Do not use an open flame.

After piping has been checked for leaks, fully purge gas pipes to remove air.

GAS PRESSURES (ALL MODELS):

The gas pressure should be set at 4” W.C. (Water Column) (0.8 kPa) for natural gas and 10” W.C. (2.75 kPa) for propane gas. If incoming pressure exceeds ½ PSI (3.45 kPa), an additional pressure regulator must be installed.

TESTING THE GAS SUPPLY PIPING SYSTEM:

When test pressures exceed ½ PSI (3.45 kPa), the fryer and its individual shutoff valve must be disconnected from the gas supply piping system.

When test pressures are ½ PSI (3.45 kPa) or less, the fryer must be isolated from the gas supply piping system by closing its individual shutoff valve.

Fryers with Casters:

Separate instructions for installing casters are included with the casters:

ŠThe installation shall be made with a connector that complies with the

Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 or Connectors for Moveable Gas Appliances, CAN/CGA-6.16, and a quick-disconnect device that complies with the Standard for Quick-Disconnect Devices for Use with Gas Fuel, ANSI z21.41 or Quick-Disconnect Devices for Use with Gas Fuel, CANI-6.9.

VULCAN-HART

F-32934 Rev. B (June 2008)

-8-

Image 8
Contents Installation & Operational Manual Important for Your Safety Table of Contents Introduction Ordering PartsUnpacking GeneralInstallation Fryer Model No Device Serial NoCodes and Standards ClearancesLocation United StatesCanada AssemblyFlue Connection Testing the GAS Supply Piping System GAS ConnectionGAS Pressures ALL Models Fryers with CastersElectrical Connection OVER-TEMPERATURE Shutdown CleaningLeveling the Fryer OperationFilling Tank with Shortening Basic Frying InstructionFry Basket Capacity Extending Shortening LifeFry Basket Guidelines Start Button Turning on the FryerTurning OFF the Fryer Extended Shutdown Filtering the OILDraining the Tank Boil OUT ProcedureWeekly or when oil is replaced Cleaning GAS KleenScreen Plus Models Filtering Instructions for KleenScreen Plus Fryers Same Suction Tube Do not Wash Fabric Envelope StepFiltering Procedure OperationQuick Start Guide for Solid State Knob Controls Filtering in 6 Easy Steps Flush and Discard Filtering TIPRemoving Excess Debris from the Screen Filter Boil OUT Procedure Thermal Overload Protection ButtonMaintenance Service in the US and CanadaFlue Vent Inspection Australia