Liebert XDP160RA, XDP160RM, XDP160RC user manual Maintenance-Basic Settings screen, page 1

Page 50

Liebert iCOM Control—Firmware Version XP1.00.010.STD

Figure 44 Maintenance—Basic Settings screen, page 1 of 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

 

Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year time span.

Max Bonus—Increases the time until the next required maintenance. Service personnel should assign a bonus when a service visit finds all components working optimally.

Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign a penalty when a service visit finds excessive wear on components.

Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of the last visit.

Service Engineer—Provides a label for the service representative to list either the company name or representative’s name.

Confirm PM—Confirms that the service representative has completed the preventive maintenance and resets the next maintenance date.

Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus set in the Liebert iCOM control.

44

Image 50
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Start the Liebert XDP with Liebert Icom Alarm Descriptions and SolutionsSpecifications Figures Tables Important Safety Instructions = 460V-3ph-60Hz Place holder Example XDP160RAPumping Unit Redundancy Place holder Revision Level Liebert Product/System Description General Product InformationEquipment Inspection Minimum LoadEquipment Handling Handling the Liebert XDP While it is on Skid and PackagedRemoving the Unit from the Skid Using a Forklift Unpacking the Liebert XDPRemoving the Unit from the Skid using Rigging Use a forklift to remove the Liebert XDP from the skidMoving the Liebert XDP Using Piano Jacks Spreader Bars BracketRemoving the Unit from the Piano Jacks Securing the Liebert XDP to piano jacksPositioning the Liebert XDP Liebert XDP dimensionsMechanical Considerations Model Pipe Connection Point 50/60 Hz Electrical ConsiderationsUnit piping outlet connection sizes, inches, OD Cu Connecting High-Voltage Cables Front view of Liebert XDP and electrical enclosureHigh voltage connections-60Hz Extra Low Voltage ELV Connections High voltage connections-50HzConnecting the remote temperature/humidity sensors DIP Switch and Jumper Settings for Remote Sensors DIP switch and jumper settingsField Connections-Optional for All Units Liebert XDP extra low voltage field connections pointsRemote Sensor Installation-Proper Placement Suggested remote sensor placementRecommended Pipe Size European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes Supply, return pipe sizes for refrigerant loopLiebert XDP Interconnection with Liebert XD Cooling Modules Piping Installation MethodsPiping Installation-R-134a Pumped Circuit Liebert XDPBypass flow controllers for a Liebert XDP-based system Piping MainsBypass Flow Controller Required Number of OpenPiping Details-Shutoff/Isolation Valves Bypass flow controller arrangementFloor Supply Return Liebert Evacuation and Leak Check-R-134a Pumped CircuitInsulation Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Checklist for Proper Installation Liebert iCOM Components and Functions Escape Key Down Arrow KeyIcon Key Name Function Display Lamp IndicatorsKeyboard icons and functions Unit Sensor a Sensor B Pump Operation Roo m Data Room Data Accessing Menus and Settings Viewing DataNavigating Through the Liebert iCOM Display Cooling Module Overview ACK High Chilled Water TempEntering the Password Entering the passwordHighlight the setting to be changed by pressing Enter Changing Liebert iCOM’s Display SettingsChanging Operational Settings English USGraphical Data Record Liebert iCOM User Menu Icons and LegendLiebert XDP User Menu screen Event Log Liebert iCOM User Menu ScreensSpare Parts SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 Online XDV8SKXDH32SK XDO20SK 20 KW Service Mode Liebert iCOM Service Menu Icons and Legend Setpoints Maintenance Diagnostics Set Alarms SettingsLiebert iCOM Service Menu Screens Liebert XDP Service Menu screenLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 LOW Temp Sensor a Enable ALM Delay EN-DIS TypeHigh Temp Sensor a Enable ALM High Temp Sensor B Enable ALMSupply Refrigerant Sensor Enable ALM High Refrigerant Temp Enable ALMLOW Refrigerant Temp Enable ALM Loss of Flow Pump Enable ALMCustomer Input Enable ALM Condensation Detected Enable ALMFAN Failure Enable ALM Smoke Detected Enable ALMS601 S612 S801 MAC GBPSystem/Network Setup screen-Unit, page 1 UnitS834 S835 S401 Local Module Shutdown Enable ALM Node ID Delay EN-DIS TypeCondensation Detected Enable Sensor Failure Enable ALMNode ID Delay EN-DIS Type Indicator Lights Description Green Red Checklist for Liebert XDP StartupLiebert XDP pump light indicator-208V and 400V units Starting the Liebert XDP with Liebert iCOM Controller System R-134a liquid level at 160kW loadAlarm Descriptions Alarm Descriptions and Solutions Unit Is Off By High CW Temp System Shutdown CausesUnit Is Off By Refrig Sens Fail Unit Is Off By Pump Short CycleTroubleshooting the Liebert XDP Symptom Possible Cause Check or RemedySee Clogged Filter Dryer and/or Impeller symptom Maintenance Fluorinated Greenhouse Gas RequirementsLiebert XDP160 specifications Liebert Corporation Dearborn Drive Box Columbus, OH 2006/42/EC 2004/108/EC 2006/95/EC 97/23/ECTwor k Ne tIs t Care