Alarm Descriptions and Solutions
SMOKE
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
SUPPLY CW SENSOR
SUPPLY REFRIGERANT SENSOR
UNIT CODE
WATER UNDER
6.2Warning Descriptions
LOSS OF
PUMP 1 HRS
PUMP 2 HRS
6.3System Shutdown Causes
Unit Is Off By Refrig Sens Fail
The control has lost its signal from the refrigerant temperature sensor. The control has no way of controlling the refrigerant temperature, so the unit is shut off. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
Unit Is Off By High CW Temp
The entering chilled water temperature is too high to keep the refrigerant pump(s) running normally. If a HIGH CW TEMP alarm occurs and the refrigerant pump loses flow (differential pressure), then the Liebert XDP will go into a
Unit Is Off By Pump Short Cycle
The control was unable to get a pump started upon startup or after a loss of differential pressure. The control looks at the SHORT CYCLE time delay. If it cannot establish differential pressure within that amount of time, the unit is shut down. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.
Unit Is Off By Low Refrig Temp
The control was unable to raise the refrigerant temperature to the calculated refrigerant temperature control point. The unit is shut down because if the control cannot raise the refrigerant temperature to the calculated refrigerant temperature control point, water may condense on the refrigerant piping and receiving coils. Main power (disconnect switch) must be turned Off, then back On to clear this alarm.