Liebert XDP160RM, XDP160RC Liebert iCOM Service Menu Screens, Liebert XDP Service Menu screen

Page 48

Liebert iCOM Control—Firmware Version XP1.00.010.STD

Figure 42 Liebert XDP Service Menu screen

°C / °F

+

 

SET

% RH

 

WELLNESS

SERVICE

ALARMS

SET

 

NETWORK

SET

XDIO

 

+/-

UP

 

 

 

 

 

 

to change level

to navigate

to open requested menu

ESC to unselect

4.10Liebert iCOM Service Menu Screens

Service menus allow customized settings for site operations. Service Menu screens employ a coding that begins with “S” and is followed by parameters and information, such as settings. Gaining access to most Service Menus requires entering a password; the Service Menu password is 5010; see 4.3.3 - Entering the Password for assistance.

The Liebert iCOM control firmware is being updated constantly. As a result, the Service Menu parameters in this manual may be slightly different from what is shown on a cooling unit’s display. Check www.liebert.com for the latest Liebert iCOM user manual updates.

Figure 43 Setpoints screen

 

 

 

 

 

 

 

 

 

 

UNIT 01

 

 

S101

PASSWORD (Actual Level 0)

????

 

 

S102

Min Room Temperature Setpoint

60.0°F

 

 

S103

Temperature Control Type

Intelligent

 

 

S104

Temperature Proportional Band

7.0°F

 

 

S105

Temperature Integration Tiime

min

 

 

S106

Temperature Derivative

sec

 

 

S107

Dewpoint Margin

4.0°F

 

 

S108

Minimum Control Point

50.0°F

 

 

S109

Min Percent Cooling Setpoint

10%

 

 

S110

 

 

 

 

 

S111

 

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

 

42

Image 48
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Alarm Descriptions and Solutions SpecificationsStart the Liebert XDP with Liebert Icom Figures Tables Important Safety Instructions Example XDP160RA Pumping Unit Redundancy Place holder Revision Level Liebert= 460V-3ph-60Hz Place holder General Product Information Equipment InspectionProduct/System Description Minimum LoadEquipment Handling Handling the Liebert XDP While it is on Skid and PackagedRemoving the Unit from the Skid Using a Forklift Unpacking the Liebert XDPRemoving the Unit from the Skid using Rigging Use a forklift to remove the Liebert XDP from the skidMoving the Liebert XDP Using Piano Jacks Spreader Bars BracketRemoving the Unit from the Piano Jacks Securing the Liebert XDP to piano jacksLiebert XDP dimensions Mechanical ConsiderationsPositioning the Liebert XDP Electrical Considerations Unit piping outlet connection sizes, inches, OD CuModel Pipe Connection Point 50/60 Hz Connecting High-Voltage Cables Front view of Liebert XDP and electrical enclosureHigh voltage connections-60Hz Extra Low Voltage ELV Connections High voltage connections-50HzConnecting the remote temperature/humidity sensors DIP Switch and Jumper Settings for Remote Sensors DIP switch and jumper settingsField Connections-Optional for All Units Liebert XDP extra low voltage field connections pointsRemote Sensor Installation-Proper Placement Suggested remote sensor placementEuropean Union Fluorinated Greenhouse Gas Requirements Connection SizesRecommended Pipe Size Supply, return pipe sizes for refrigerant loopPiping Installation Methods Piping Installation-R-134a Pumped CircuitLiebert XDP Interconnection with Liebert XD Cooling Modules Liebert XDPPiping Mains Bypass Flow ControllerBypass flow controllers for a Liebert XDP-based system Required Number of OpenPiping Details-Shutoff/Isolation Valves Bypass flow controller arrangementEvacuation and Leak Check-R-134a Pumped Circuit InsulationFloor Supply Return Liebert Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsCalculating Refrigerant Charge-Example Calculating refrigerant charge-exampleWorksheet to calculate refrigerant charge Checklist for Proper Installation Liebert iCOM Components and Functions Escape Key Down Arrow KeyDisplay Lamp Indicators Keyboard icons and functionsIcon Key Name Function Accessing Menus and Settings Viewing Data Navigating Through the Liebert iCOM DisplayUnit Sensor a Sensor B Pump Operation Roo m Data Room Data Cooling Module Overview ACK High Chilled Water TempEntering the Password Entering the passwordChanging Liebert iCOM’s Display Settings Changing Operational SettingsHighlight the setting to be changed by pressing Enter English USGraphical Data Record Liebert iCOM User Menu Icons and LegendLiebert XDP User Menu screen Liebert iCOM User Menu Screens Spare PartsEvent Log SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 Online XDV8SKXDH32SK XDO20SK 20 KWLiebert iCOM Service Menu Icons and Legend Setpoints Maintenance Diagnostics Set AlarmsService Mode SettingsLiebert iCOM Service Menu Screens Liebert XDP Service Menu screenLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 Delay EN-DIS Type High Temp Sensor a Enable ALMLOW Temp Sensor a Enable ALM High Temp Sensor B Enable ALMHigh Refrigerant Temp Enable ALM LOW Refrigerant Temp Enable ALMSupply Refrigerant Sensor Enable ALM Loss of Flow Pump Enable ALMCondensation Detected Enable ALM FAN Failure Enable ALMCustomer Input Enable ALM Smoke Detected Enable ALMS601 S612 S801 MAC GBPSystem/Network Setup screen-Unit, page 1 UnitS834 S835 S401 Node ID Delay EN-DIS Type Condensation Detected EnableLocal Module Shutdown Enable ALM Sensor Failure Enable ALMNode ID Delay EN-DIS Type Checklist for Liebert XDP Startup Liebert XDP pump light indicator-208V and 400V unitsIndicator Lights Description Green Red Starting the Liebert XDP with Liebert iCOM Controller System R-134a liquid level at 160kW loadAlarm Descriptions Alarm Descriptions and Solutions System Shutdown Causes Unit Is Off By Refrig Sens FailUnit Is Off By High CW Temp Unit Is Off By Pump Short CycleTroubleshooting the Liebert XDP Symptom Possible Cause Check or RemedySee Clogged Filter Dryer and/or Impeller symptom Maintenance Fluorinated Greenhouse Gas RequirementsLiebert XDP160 specifications Liebert Corporation Dearborn Drive Box Columbus, OH 2006/42/EC 2004/108/EC 2006/95/EC 97/23/ECNe t Is tTwor k Care