Page 62

Liebert iCOM Control—Firmware Version XP1.00.010.STD

Humidity Sensor B—Adjusts the humidity reading from the actual remote sensor designated as Sensor B to compensate for any error of the sensor or to match other sensors in the room.

Calibrated Humidity Sensor B—Displays the adjusted humidity value of the remote CAN Temp Humidity sensor designated as Sensor B. This value is the actual sensor reading plus or minus the offset Humidity Sensor B.

Figure 61 Sensor Calibration/Setup screen, page 2 of 3

 

 

 

 

 

S612

PASSWORD (Actual Level

0)

????

S613

Supply Refrigerant Sensor

 

+0.0°F

S614

Calibrated Supply Refrigerant Sensor

58.5°F

S615

 

 

 

 

S616

 

 

 

 

S617

Supply Chilled Water Sensor

 

+0.0°F

S618

Calibrated Supply Chilled Water Sensor

60.1°F

S619

 

 

 

 

S620

 

 

 

 

S621

 

 

 

 

S622

 

 

 

 

 

 

for next/previous unit

to select parameter

then

to change parameter

 

to confirm

 

 

 

 

 

Supply Refrigerant Sensor—Adjusts the temperature reading from the actual supply refrigerant sensor to compensate for any error of the sensor.

Calibrated Supply Refrigerant Sensor—Displays the adjusted temperature value of the supply refrigerant sensor. This value is the actual sensor reading plus or minus the offset Supply Refrigerant Sensor.

Supply Chilled Water Sensor—Adjusts the temperature reading from the actual supply chilled water sensor to compensate for any error of the sensor.

Calibrated Chilled Water Sensor—Displays the adjusted temperature value of the supply chilled water sensor. This value is the actual sensor reading plus or minus the offset Supply Chilled Water Sensor.

Figure 62 Sensor Calibration/Setup screen, page 3 of 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S623

PASSWORD (Actual Level 0)

????

 

 

 

 

S624

Supply Refrigerant Sensor 0%

30.0°F

 

 

 

 

S625

Supply Refrigerant Sensor 100%

90.0°F

 

 

 

 

S626

 

 

 

 

 

 

 

S627

 

 

 

 

 

 

 

S628

 

 

 

 

 

 

 

S629

 

 

 

 

 

 

 

S630

 

 

 

 

 

 

 

S631

 

 

 

 

 

 

 

S632

 

 

 

 

 

 

 

S633

 

 

 

 

 

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

 

 

then

to change parameter

to confirm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56

Image 62
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Start the Liebert XDP with Liebert Icom Alarm Descriptions and SolutionsSpecifications Figures Tables Important Safety Instructions = 460V-3ph-60Hz Place holder Example XDP160RAPumping Unit Redundancy Place holder Revision Level Liebert Product/System Description General Product InformationEquipment Inspection Minimum LoadEquipment Handling Handling the Liebert XDP While it is on Skid and PackagedRemoving the Unit from the Skid Using a Forklift Unpacking the Liebert XDPRemoving the Unit from the Skid using Rigging Use a forklift to remove the Liebert XDP from the skidMoving the Liebert XDP Using Piano Jacks Spreader Bars BracketRemoving the Unit from the Piano Jacks Securing the Liebert XDP to piano jacksPositioning the Liebert XDP Liebert XDP dimensionsMechanical Considerations Model Pipe Connection Point 50/60 Hz Electrical ConsiderationsUnit piping outlet connection sizes, inches, OD Cu Connecting High-Voltage Cables Front view of Liebert XDP and electrical enclosureHigh voltage connections-60Hz Extra Low Voltage ELV Connections High voltage connections-50HzConnecting the remote temperature/humidity sensors DIP Switch and Jumper Settings for Remote Sensors DIP switch and jumper settingsField Connections-Optional for All Units Liebert XDP extra low voltage field connections pointsRemote Sensor Installation-Proper Placement Suggested remote sensor placementRecommended Pipe Size European Union Fluorinated Greenhouse Gas RequirementsConnection Sizes Supply, return pipe sizes for refrigerant loopLiebert XDP Interconnection with Liebert XD Cooling Modules Piping Installation MethodsPiping Installation-R-134a Pumped Circuit Liebert XDPBypass flow controllers for a Liebert XDP-based system Piping MainsBypass Flow Controller Required Number of OpenPiping Details-Shutoff/Isolation Valves Bypass flow controller arrangementFloor Supply Return Liebert Evacuation and Leak Check-R-134a Pumped CircuitInsulation Filling the Pumped Circuit-R-134a System refrigerant charge for the supply and return mainsWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Checklist for Proper Installation Liebert iCOM Components and Functions Escape Key Down Arrow KeyIcon Key Name Function Display Lamp IndicatorsKeyboard icons and functions Unit Sensor a Sensor B Pump Operation Roo m Data Room Data Accessing Menus and Settings Viewing DataNavigating Through the Liebert iCOM Display Cooling Module Overview ACK High Chilled Water TempEntering the Password Entering the passwordHighlight the setting to be changed by pressing Enter Changing Liebert iCOM’s Display SettingsChanging Operational Settings English USGraphical Data Record Liebert iCOM User Menu Icons and LegendLiebert XDP User Menu screen Event Log Liebert iCOM User Menu ScreensSpare Parts SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 Online XDV8SKXDH32SK XDO20SK 20 KWService Mode Liebert iCOM Service Menu Icons and LegendSetpoints Maintenance Diagnostics Set Alarms SettingsLiebert iCOM Service Menu Screens Liebert XDP Service Menu screenLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 LOW Temp Sensor a Enable ALM Delay EN-DIS TypeHigh Temp Sensor a Enable ALM High Temp Sensor B Enable ALM Supply Refrigerant Sensor Enable ALM High Refrigerant Temp Enable ALM LOW Refrigerant Temp Enable ALM Loss of Flow Pump Enable ALMCustomer Input Enable ALM Condensation Detected Enable ALMFAN Failure Enable ALM Smoke Detected Enable ALMS601 S612 S801 MAC GBPSystem/Network Setup screen-Unit, page 1 UnitS834 S835 S401 Local Module Shutdown Enable ALM Node ID Delay EN-DIS TypeCondensation Detected Enable Sensor Failure Enable ALMNode ID Delay EN-DIS Type Indicator Lights Description Green Red Checklist for Liebert XDP StartupLiebert XDP pump light indicator-208V and 400V units Starting the Liebert XDP with Liebert iCOM Controller System R-134a liquid level at 160kW loadAlarm Descriptions Alarm Descriptions and Solutions Unit Is Off By High CW Temp System Shutdown CausesUnit Is Off By Refrig Sens Fail Unit Is Off By Pump Short CycleTroubleshooting the Liebert XDP Symptom Possible Cause Check or RemedySee Clogged Filter Dryer and/or Impeller symptom Maintenance Fluorinated Greenhouse Gas RequirementsLiebert XDP160 specifications Liebert Corporation Dearborn Drive Box Columbus, OH 2006/42/EC 2004/108/EC 2006/95/EC 97/23/ECTwor k Ne tIs t Care