Liebert XDP160RC Changing Liebert iCOM’s Display Settings, Changing Operational Settings, Xdp

Page 37

Liebert iCOM Control—Firmware Version XP1.00.010.STD

4.4Changing Liebert iCOM’s Display Settings

No password is required to change the way Liebert iCOM displays data. The Display Setup controls how the unit shows data, such as temperature, date and time.

To change the display settings:

1.From the home screen, press the Enter key to view the User Menu (see Figure 29).

2.Press Enter again to highlight the first icon.

3.Use the keyboard’s arrow keys to move to the Display Setup icon.

4.Once that icon is highlighted, press Enter again to open that menu.

5.Press the Enter key to select the first setting.

Either change that setting or navigate to another setting with the Up and Down arrow keys.

6.Once the desired setting is highlighted, press the Enter key to access that parameter’s display setting options.

7.Use the Up and Down arrow keys to make changes.

8.Press the Enter key to accept the changes.

9.Press the ESC key twice to return to Liebert iCOM’s user menu.

Figure 28 Display setup screen

Highlight the setting to be changed by pressing Enter.

 

 

 

 

 

 

DISPLAY SETUP

SYSTEM

 

 

 

Language

ENGLISH (US)

 

 

U401

 

 

U402

Date

8/27/2012

 

 

U403

Time

15:03:17

 

 

U404

Temperature Indication

°C

 

 

U405

Display Contrast

50

 

 

U406

Buzzer Frequency

Off/ 50

 

 

U407

Backlite Off after

5 min

 

 

U408

Screen

XDP

 

 

U409

 

 

 

 

U410

Display Colors

Normal

 

 

U411

Date Format

mm/dd/yyyy

 

 

 

 

 

 

 

 

 

for next/previous unit

to select parameter

 

 

then to change parameter

to confirm

 

 

 

 

 

 

4.5Changing Operational Settings

Changes to the Liebert XDP’s operation settings in the Set Alarms and Setpoints menus require a password.

1.From the home screen, press the Enter key to view the User Menu (see Figure 29).

2.Press Enter again to highlight the first icon.

3.Use the keyboard’s arrow keys to move to the icon for the data you wish to change.

4.Once that icon is highlighted, press Enter again to open that menu. If a password is required, see 4.3.3 - Entering the Password.

5.After entering the password, use the Up and Down arrow keys to scroll to and highlight the operational setting to be changed.

6.Press Enter to highlight the values for that setting.

7.Use the Up and Down arrow keys to change the value.

8.Press Enter to accept the change. (The value will no longer be highlighted.)

9.Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)

10.Press ESC again to move to previous screens.

31

Image 37
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Specifications Alarm Descriptions and SolutionsStart the Liebert XDP with Liebert Icom Figures Tables Important Safety Instructions Pumping Unit Redundancy Place holder Revision Level Liebert Example XDP160RA= 460V-3ph-60Hz Place holder Equipment Inspection General Product InformationProduct/System Description Minimum LoadHandling the Liebert XDP While it is on Skid and Packaged Equipment HandlingUnpacking the Liebert XDP Removing the Unit from the Skid Using a ForkliftUse a forklift to remove the Liebert XDP from the skid Removing the Unit from the Skid using RiggingSpreader Bars Bracket Moving the Liebert XDP Using Piano JacksSecuring the Liebert XDP to piano jacks Removing the Unit from the Piano JacksMechanical Considerations Liebert XDP dimensionsPositioning the Liebert XDP Unit piping outlet connection sizes, inches, OD Cu Electrical ConsiderationsModel Pipe Connection Point 50/60 Hz Front view of Liebert XDP and electrical enclosure Connecting High-Voltage CablesHigh voltage connections-60Hz High voltage connections-50Hz Extra Low Voltage ELV ConnectionsConnecting the remote temperature/humidity sensors DIP switch and jumper settings DIP Switch and Jumper Settings for Remote SensorsLiebert XDP extra low voltage field connections points Field Connections-Optional for All UnitsSuggested remote sensor placement Remote Sensor Installation-Proper PlacementConnection Sizes European Union Fluorinated Greenhouse Gas RequirementsRecommended Pipe Size Supply, return pipe sizes for refrigerant loopPiping Installation-R-134a Pumped Circuit Piping Installation MethodsLiebert XDP Interconnection with Liebert XD Cooling Modules Liebert XDPBypass Flow Controller Piping MainsBypass flow controllers for a Liebert XDP-based system Required Number of OpenBypass flow controller arrangement Piping Details-Shutoff/Isolation ValvesInsulation Evacuation and Leak Check-R-134a Pumped CircuitFloor Supply Return Liebert System refrigerant charge for the supply and return mains Filling the Pumped Circuit-R-134aCalculating refrigerant charge-example Calculating Refrigerant Charge-ExampleWorksheet to calculate refrigerant charge Checklist for Proper Installation Escape Key Down Arrow Key Liebert iCOM Components and FunctionsKeyboard icons and functions Display Lamp IndicatorsIcon Key Name Function Navigating Through the Liebert iCOM Display Accessing Menus and Settings Viewing DataUnit Sensor a Sensor B Pump Operation Roo m Data Room Data ACK High Chilled Water Temp Cooling Module OverviewEntering the password Entering the PasswordChanging Operational Settings Changing Liebert iCOM’s Display SettingsHighlight the setting to be changed by pressing Enter English USLiebert iCOM User Menu Icons and Legend Graphical Data RecordLiebert XDP User Menu screen Spare Parts Liebert iCOM User Menu ScreensEvent Log SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 XDV8SK OnlineXDO20SK 20 KW XDH32SKSetpoints Maintenance Diagnostics Set Alarms Liebert iCOM Service Menu Icons and LegendService Mode SettingsLiebert XDP Service Menu screen Liebert iCOM Service Menu ScreensLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 High Temp Sensor a Enable ALM Delay EN-DIS TypeLOW Temp Sensor a Enable ALM High Temp Sensor B Enable ALMLOW Refrigerant Temp Enable ALM High Refrigerant Temp Enable ALMSupply Refrigerant Sensor Enable ALM Loss of Flow Pump Enable ALMFAN Failure Enable ALM Condensation Detected Enable ALMCustomer Input Enable ALM Smoke Detected Enable ALMS601 S612 S801 GBP MACUnit System/Network Setup screen-Unit, page 1S834 S835 S401 Condensation Detected Enable Node ID Delay EN-DIS TypeLocal Module Shutdown Enable ALM Sensor Failure Enable ALMNode ID Delay EN-DIS Type Liebert XDP pump light indicator-208V and 400V units Checklist for Liebert XDP StartupIndicator Lights Description Green Red System R-134a liquid level at 160kW load Starting the Liebert XDP with Liebert iCOM ControllerAlarm Descriptions Alarm Descriptions and Solutions Unit Is Off By Refrig Sens Fail System Shutdown CausesUnit Is Off By High CW Temp Unit Is Off By Pump Short CycleSymptom Possible Cause Check or Remedy Troubleshooting the Liebert XDPSee Clogged Filter Dryer and/or Impeller symptom Fluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications 2006/42/EC 2004/108/EC 2006/95/EC 97/23/EC Liebert Corporation Dearborn Drive Box Columbus, OHIs t Ne tTwor k Care

XDP160RA, XDP160RC, XDP160RM specifications

The Liebert XDP series is an innovative line of uninterruptible power supplies (UPS) designed to safeguard critical IT equipment and ensure reliability in demanding environments. The XDP160RM, XDP160RC, and XDP160RA models are distinguished by their robust features and advanced technologies, making them ideal for data centers, server rooms, and telecommunications.

One of the standout features of the Liebert XDP series is its high power density. The XDP160RM, XDP160RC, and XDP160RA models provide 160 kVA of power in a compact design, occupying minimal floor space. This efficient design maximizes data center performance without compromising on reliability.

All three models utilize advanced digital signal processing (DSP) technology that enhances system performance and efficiency. The DSP technology ensures high efficiency rates, often exceeding 95% in online mode. This not only reduces energy costs but also minimizes heat output, contributing to a more sustainable operational environment.

The Liebert XDP series is equipped with multiple output configurations, allowing for versatile installation options. The modular architecture of the UPS systems allows for easy scalability to meet future power demands without the need for complete system replacement. This flexibility is crucial for businesses expecting growth or changes in IT infrastructure.

Another important aspect of the XDP160RM, XDP160RC, and XDP160RA is their advanced battery management systems, which optimize battery performance and longevity. The integrated smart battery charging technology prevents overcharging and extends battery life, ensuring that the UPS is always ready during power interruptions.

Additionally, the systems are designed with user-friendly interfaces that facilitate ease of monitoring and management. With real-time data on power usage, battery status, and overall system health, IT administrators can quickly address any issues that arise. The monitoring capabilities extend to remote access, enabling users to manage the UPS systems from virtually anywhere.

The Liebert XDP series also incorporates enhanced safety features, including fault detection and automated alerts, which further bolster reliability. With a strong commitment to maintaining uptime and safeguarding critical operations, the XDP models are a wise investment for any organization reliant on continuous power availability.

In conclusion, the Liebert XDP160RM, XDP160RC, and XDP160RA UPS systems are engineered to deliver exceptional power protection through high efficiency, advanced technologies, and user-friendly management features. These models are positioned to meet the rigorous demands of modern IT environments, ensuring that businesses can maintain operations without interruption.