Liebert XDP160RA, XDP160RM, XDP160RC user manual Filling the Pumped Circuit-R-134a

Page 29

Piping

3.6Filling the Pumped Circuit—R-134a

Using a refrigerant pump or cylinder heater pads will speed the charging process.

1.Connect a charging manifold to the service port of the receiver outlet valve or to the suction and discharge side of the pump.

2.Purge the hoses.

3.Calculate the amount of R-134a refrigerant needed to charge the system, using the values in Tables 6, 7, 8 and 9; for assistance, refer to 3.6.1 - Calculating Refrigerant Charge— Example. The section includes a worksheet to calculate system refrigerant charge requirements.

4.Weigh in the calculated charge.

5.After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium. Observe the refrigerant level through the sight glasses of the receiver. The level should be above the second sight glass at a minimum when the Liebert XDP is off.

6.If the refrigerant level is improper, the charge must be adjusted.

If the level is too high or too low, recalculate the required charge and reduce or increase the amount as needed to reach the proper level.

NOTE

All lengths in Tables 6, 7 and 8 are actual pipe lengths, not equivalent pipe lengths.

NOTE

System refrigerant volume calculations derived from Tables 6, 7, 8 and 9 are based on a fully loaded system. Additional charge may be required for lightly loaded systems.

Table 6 System R-134a charge for a Liebert XDP with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR

Refrigerant Charge, lb. (kg)

Per Liebert XD Unit

(Excludes Connector Lines to and from Liebert XD Cooling Module)

1.41 lb. (0.64kg)

Liebert XDCF

5.32 lb. (2.41kg)

Liebert XDH

3.55 lb. (1.61kg)

Liebert XDO

157 lb. (71.2kg)

Liebert XDP

4 lb. (1.8kg)

Liebert XDR

2.32 lb. (1.05kg)

Liebert XDV

Table 7

System refrigerant charge for the supply and return mains

 

 

 

Refrigerant Charge,

 

 

lb/foot (kg/m)

Supply/Return Main Length and Diameter

 

0.45 (0.67)

Main supply actual length per 1-1/8" OD copper tubing

 

0.68 (1.01)

Main supply actual length per 1-3/8" OD copper tubing

 

0.28 (0.42)

Main return actual length per 2-1/8" OD copper tubing

 

0.43 (0.64)

Main return actual length per 2-5/8" OD copper tubing

 

Before beginning, verify that the system is not equipped with pre-charged Liebert XD Flex Pipe.

Table 8 R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR

Refrigerant

 

Charge, lb/foot (kg/m)

Hard-Piped Connector Length and Diameter

0.08 (0.12)

1/2" OD Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR supply connector

actual length

 

0.13 (0.19)

5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length

0.26 (0.39)

7/8" OD Liebert XDO/Liebert XDH/Liebert XDR supply connector actual length

0.02 (0.03)

5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length

0.04 (0.06)

7/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length

0.04 (0.06)

7/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length

0.07 (0.1)

1-1/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XDR return connector actual length

23

Image 29
Contents Liebert XDP with Liebert iCOM Control Page Table of Contents Start the Liebert XDP with Liebert Icom Alarm Descriptions and SolutionsSpecifications Figures Tables Important Safety Instructions = 460V-3ph-60Hz Place holder Example XDP160RAPumping Unit Redundancy Place holder Revision Level Liebert Equipment Inspection General Product InformationProduct/System Description Minimum LoadHandling the Liebert XDP While it is on Skid and Packaged Equipment HandlingUnpacking the Liebert XDP Removing the Unit from the Skid Using a ForkliftUse a forklift to remove the Liebert XDP from the skid Removing the Unit from the Skid using RiggingSpreader Bars Bracket Moving the Liebert XDP Using Piano JacksSecuring the Liebert XDP to piano jacks Removing the Unit from the Piano JacksPositioning the Liebert XDP Liebert XDP dimensionsMechanical Considerations Model Pipe Connection Point 50/60 Hz Electrical ConsiderationsUnit piping outlet connection sizes, inches, OD Cu Front view of Liebert XDP and electrical enclosure Connecting High-Voltage CablesHigh voltage connections-60Hz High voltage connections-50Hz Extra Low Voltage ELV ConnectionsConnecting the remote temperature/humidity sensors DIP switch and jumper settings DIP Switch and Jumper Settings for Remote SensorsLiebert XDP extra low voltage field connections points Field Connections-Optional for All UnitsSuggested remote sensor placement Remote Sensor Installation-Proper PlacementConnection Sizes European Union Fluorinated Greenhouse Gas RequirementsRecommended Pipe Size Supply, return pipe sizes for refrigerant loopPiping Installation-R-134a Pumped Circuit Piping Installation MethodsLiebert XDP Interconnection with Liebert XD Cooling Modules Liebert XDPBypass Flow Controller Piping MainsBypass flow controllers for a Liebert XDP-based system Required Number of OpenBypass flow controller arrangement Piping Details-Shutoff/Isolation ValvesFloor Supply Return Liebert Evacuation and Leak Check-R-134a Pumped CircuitInsulation System refrigerant charge for the supply and return mains Filling the Pumped Circuit-R-134aWorksheet to calculate refrigerant charge Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Checklist for Proper Installation Escape Key Down Arrow Key Liebert iCOM Components and FunctionsIcon Key Name Function Display Lamp IndicatorsKeyboard icons and functions Unit Sensor a Sensor B Pump Operation Roo m Data Room Data Accessing Menus and Settings Viewing DataNavigating Through the Liebert iCOM Display ACK High Chilled Water Temp Cooling Module OverviewEntering the password Entering the PasswordChanging Operational Settings Changing Liebert iCOM’s Display SettingsHighlight the setting to be changed by pressing Enter English USLiebert iCOM User Menu Icons and Legend Graphical Data RecordLiebert XDP User Menu screen Event Log Liebert iCOM User Menu ScreensSpare Parts SET Alarms page 1 Sensor Data screen, page 1 Sensor Data screen, page 2 U401 U402 XDV8SK OnlineXDO20SK 20 KW XDH32SKSetpoints Maintenance Diagnostics Set Alarms Liebert iCOM Service Menu Icons and LegendService Mode SettingsLiebert XDP Service Menu screen Liebert iCOM Service Menu ScreensLiebert iCOM Control-Firmware Version XP1.00.010.STD Maintenance-Basic Settings screen, page 1 Maintenance-Pump 1 Settings screen, page 2 Maintenance-Pump 2 Settings screen, page 3 Diagnostics/Service Mode screen, page 1 Manual Mode Control Type-Not currently used Diagnostics/Service Mode screen, page 5 Set Alarms screen, page 1 Set Alarms screen, page 2 High Temp Sensor a Enable ALM Delay EN-DIS TypeLOW Temp Sensor a Enable ALM High Temp Sensor B Enable ALMLOW Refrigerant Temp Enable ALM High Refrigerant Temp Enable ALMSupply Refrigerant Sensor Enable ALM Loss of Flow Pump Enable ALMFAN Failure Enable ALM Condensation Detected Enable ALMCustomer Input Enable ALM Smoke Detected Enable ALMS601 S612 S801 GBP MACUnit System/Network Setup screen-Unit, page 1S834 S835 S401 Condensation Detected Enable Node ID Delay EN-DIS TypeLocal Module Shutdown Enable ALM Sensor Failure Enable ALMNode ID Delay EN-DIS Type Indicator Lights Description Green Red Checklist for Liebert XDP StartupLiebert XDP pump light indicator-208V and 400V units System R-134a liquid level at 160kW load Starting the Liebert XDP with Liebert iCOM ControllerAlarm Descriptions Alarm Descriptions and Solutions Unit Is Off By Refrig Sens Fail System Shutdown CausesUnit Is Off By High CW Temp Unit Is Off By Pump Short CycleSymptom Possible Cause Check or Remedy Troubleshooting the Liebert XDPSee Clogged Filter Dryer and/or Impeller symptom Fluorinated Greenhouse Gas Requirements MaintenanceLiebert XDP160 specifications 2006/42/EC 2004/108/EC 2006/95/EC 97/23/EC Liebert Corporation Dearborn Drive Box Columbus, OHIs t Ne tTwor k Care

XDP160RA, XDP160RC, XDP160RM specifications

The Liebert XDP series is an innovative line of uninterruptible power supplies (UPS) designed to safeguard critical IT equipment and ensure reliability in demanding environments. The XDP160RM, XDP160RC, and XDP160RA models are distinguished by their robust features and advanced technologies, making them ideal for data centers, server rooms, and telecommunications.

One of the standout features of the Liebert XDP series is its high power density. The XDP160RM, XDP160RC, and XDP160RA models provide 160 kVA of power in a compact design, occupying minimal floor space. This efficient design maximizes data center performance without compromising on reliability.

All three models utilize advanced digital signal processing (DSP) technology that enhances system performance and efficiency. The DSP technology ensures high efficiency rates, often exceeding 95% in online mode. This not only reduces energy costs but also minimizes heat output, contributing to a more sustainable operational environment.

The Liebert XDP series is equipped with multiple output configurations, allowing for versatile installation options. The modular architecture of the UPS systems allows for easy scalability to meet future power demands without the need for complete system replacement. This flexibility is crucial for businesses expecting growth or changes in IT infrastructure.

Another important aspect of the XDP160RM, XDP160RC, and XDP160RA is their advanced battery management systems, which optimize battery performance and longevity. The integrated smart battery charging technology prevents overcharging and extends battery life, ensuring that the UPS is always ready during power interruptions.

Additionally, the systems are designed with user-friendly interfaces that facilitate ease of monitoring and management. With real-time data on power usage, battery status, and overall system health, IT administrators can quickly address any issues that arise. The monitoring capabilities extend to remote access, enabling users to manage the UPS systems from virtually anywhere.

The Liebert XDP series also incorporates enhanced safety features, including fault detection and automated alerts, which further bolster reliability. With a strong commitment to maintaining uptime and safeguarding critical operations, the XDP models are a wise investment for any organization reliant on continuous power availability.

In conclusion, the Liebert XDP160RM, XDP160RC, and XDP160RA UPS systems are engineered to deliver exceptional power protection through high efficiency, advanced technologies, and user-friendly management features. These models are positioned to meet the rigorous demands of modern IT environments, ensuring that businesses can maintain operations without interruption.